Keypad Start/Stop (Local Mode) continued:
4. If parameters were accessed or changed under Parameter Setup then the last parameter number or value will be
displayed. Scroll up or down with the
Proportional Value for Speed) and press the
5. Return to step 1 and press the
Local/Remote Modes:
In the previous section the drive was operated from the keypad
(Local Mode). If you wish to operate in remote mode you will need to
add an external Local/Remote switch. Note: To control speed in
remote mode a speed potentiometer (figure 5) can be added or the
up and down arrow keys on the keypad can be used by setting
P222=0. Plus versions can use the keypad speed potentiometer by
setting P222=3.
Parameters: Confirm DI3 is set to Local/Remote (P265=6).
Control Wiring: Local/Remote switch is N.O (normally open) and is
connected as shown in Figure 3.
2 Wire Start/Stop (Remote Mode):
Parameters:
1. Confirm DI4 is set to START/STOP (P266=4).
2. Set P229=1 (DIx) if you want the 2 wire control in local mode.
3. Confirm P230=1 (DIx) if you want the 2 wire control in remote
mode.
Control Wiring: Verify there is a jumper between XC1-1 (general
enable) and XC1-5 or the drive will not work. Jumper can be
eliminated if DI1 is set to "No Function" (P263=0). Start/Stop switch is
N.O. (normally open) and is connected as shown in Figure 3.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
or
keys to the read only parameter P002 (Frequency
key to see the value.
start key to start the drive.
4
4
Figure 3 –
Local/Remote and 2 Wire Start/Stop