Mechanical Structure - Siemens SICAM MIC System Description

Compact telecontrol system
Table of Contents

Advertisement

System Overview
2.2

Mechanical Structure

Installation takes place on a 35 mm DIN rail that is mounted horizontally or vertically on a ver-
tical standing rack. The sequence of modules from left to right or top to bottom is prescribed
as follows:
·
1 power supply module (optionally 2 for redundancy)
·
1 master control module
·
Optionally up to 8 I/O modules
The electrical connection of the modules with the power supply takes place during the process
of latching together, whereby each module can be individually replaced.
Standard Structure
Power Supply Module
SICAM RTUs, SICAM MIC System Description
MC6-054-2.00, Edition 07.2014
Master Control Module
8 I/O-Modules max.