System Components and Technical Data
5.4.1.4

AI-6310

·
Temperatures
─ Acquisition of resistance thermometers via analog inputs of a SM-0571
─ Connection of the resistance thermometers: 2-, 3-, or 4-wire technique
─ Update every 400 ms
─ Settable measuring range
− Temperaturwerte
- Input range
- Resolution
- Update grid
− Resistance values
- Input range 40...400 Ω
- Resolution 56 mΩ
- Update grid
Revision
─ Noise rejection
─ Automatic calibration
─ Calibration for 2-wire technique
─ Smoothing
─ Adaptation
− Temperature value (°C, °F), conversion using implemented curves
− Resistance (Ω)
─ Change monitoring
─ Spontaneous transmission of changes
______
*)
not supported by USIO60, USIO61
5.4.1.5
TE-6430
·
Integrated totals via counting pulses
─ 2 counting pulse inputs or
─ 1 counting pulse input and 1 transfer input
─ Inputs are galvanically insulated from logic circles and ground
─ Inputs are not galvanically insulated from each other
─ Input voltage range from 24 up to 60 V
─ Inputs are secured by means of EMC filter and protector equipment
─ Autonomous operable functions of the module are operated buffered, thus counting func-
tion and counts remain correct with a voltage failure up to 72 hours
─ Spontaneous transmission
SICAM RTUs, SICAM MIC System Description
MC6-054-2.00, Edition 07.2014
t1
-50...+350°C / -58...+662°F / (»80,31...229,67 Ω)
Pt100:
Pt100: -100...+700°C / -148...+1292°F / (»60,25...345,13 Ω)
-60...+250°C / -76...+482°F / (»69,5...289,2 Ω)
Ni100:
Pt100:
-50...+350°C 0.15°C / 0.28°F / (56 mΩ)
Pt100: -100...+700°C 0.15°C / 0.28°F / (56 mΩ)
Ni100:
-60...+250°C 0.15°C / 0.28°F / (56 mΩ)
16⅔ Hz <6,8 s
50 Hz
< 5,6 s
60 Hz
< 5,2 s
HW rev. ≥"-A"
HW rev. ="--"
16⅔ Hz < 6,8 s 16⅔ Hz < 1,68 s
50 Hz
< 5,6 s 50 Hz
60 Hz
< 5,2 s 60 Hz
*)
f
< 1,44 s
< 1,36 s
59