Return Information To Pulse Command Assignment - Siemens SICAM MIC System Description

Compact telecontrol system
Table of Contents

Advertisement

5.4.3

Return Information to Pulse Command Assignment

Type
Single information to single command
(1-pole):
DI-610x with DO-6200
Single information to single command
(1-pole):
DI-610x with DO-6212
(two DO-6212 with one DI-610x possible)
Single information to single command
(1-pole):
DI-610x with DO-6230
Single information to single command
(1.5-pole):
DI-610x with DO-6212
(two DO-6212 with one DI-610x possible)
Single information to single command
(1.5-pole):
DI-610x with DO-6230
Single information to single command
(2-pole):
DI-610x with DO-6212
(two DO-6212 with one DI-610x possible)
Single information to single command
(2-pole):
DI-610x with DO-6230
64
System Components and Technical Data
Predefined Assignment
EM IOM x – IN D00 ... command IOM y – OUT D00
EM IOM x – IN D01 ... command IOM y – OUT D01
:
EM IOM x – IN D07 ... command IOM y – OUT D07
EM IOM x – IN D10 ... command IOM y – OUT D10
EM IOM x – IN D11 ... command IOM y – OUT D11
:
EM IOM x – IN D17 ... command IOM y – OUT D17
SI IOM x – IN D00 ... command IOM y – OUT D00
SI IOM x – IN D01 ... command IOM y – OUT D01
:
SI IOM x – IN D07 ... command IOM y – OUT D07
SI IOM x – IN D10 ... command IOM z – OUT D00
SI IOM x – IN D11 ... command IOM z – OUT D01
:
SI IOM x – IN D17 ... command IOM z – OUT D07
SI IOM x – IN D00 ... command IOM y – CA00
SI IOM x – IN D01 ... command IOM y – CA01
:
SI IOM x – IN D07 ... command IOM y – CA07
SI IOM x – IN D10 ... command IOM y – CB00
SI IOM x – IN D11 ... command IOM y – CB01
:
SI IOM x – IN D17 ... command IOM y – CB07
SI IOM x – IN D00 ... command IOM y – OUT D00
SI IOM x – IN D01 ... command IOM y – OUT D01
:
SI IOM x – IN D06 ... command IOM y – OUT D06
SI IOM x – IN D10 ... command IOM z – OUT D00
SI IOM x – IN D11 ... command IOM z – OUT D01
:
SI IOM x – IN D16 ... command IOM z – OUT D06
SI IOM x – IN D00 ... command IOM y – CA00
SI IOM x – IN D01 ... command IOM y – CA01
:
SI IOM x – IN D07 ... command IOM y – CA07
SI IOM x – IN D10 ... command IOM y – CB00
SI IOM x – IN D11 ... command IOM y – CB01
:
SI IOM x – IN D17 ... command IOM y – CB07
SI IOM x – IN D00 ... command IOM y – OUT D00/D01
SI IOM x – IN D02 ... command IOM y – OUT D02/D03
SI IOM x – IN D04 ... command IOM y – OUT D04/D05
SI IOM x – IN D06 ... command IOM y – OUT D06/D07
SI IOM x – IN D10 ... command IOM z – OUT D00/D01
SI IOM x – IN D12 ... command IOM z – OUT D02/D03
SI IOM x – IN D14 ... command IOM z – OUT D04/D05
SI IOM x – IN D16 ... command IOM z – OUT D06/D07
SI IOM x – IN D00 ... command IOM y – CA00/CB00
SI IOM x – IN D01 ... command IOM y – CA01/CB01
:
SI IOM x – IN D07 ... command IOM y – CA07/CB07
SICAM RTUs, SICAM MIC System Description
:
:
:
:
:
:
:
:
:
:
:
MC6-054-2.00, Edition 07.2014

Hide quick links: