Explanation Of The Parameters - Siemens Simatic ET 200SP Manual

Analog input module ai 2xu st.
Hide thumbs

Advertisement

Parameters/address space

4.3 Explanation of the parameters

4.3
Explanation of the parameters
Diagnostics: No supply voltage L+
Enabling of the diagnostics for no or insufficient supply voltage L+.
Diagnostics: Short-circuit to ground
Diagnostics are enabled when both input signals are short-circuited in the range 1 to 5 V.
The short-circuit and underflow diagnostics can be activated simultaneously. If both
diagnostics events occur simultaneously, however, the short-circuit diagnostics suppresses
the underflow diagnostics. Short-circuit is output as the diagnostics event.
Diagnostics: Overflow
Enabling of the diagnostics when the measured value exceeds the overrange.
Diagnostics: Underflow
Enabling of the diagnostics when the measured value falls below the underrange.
Measurement type/measuring range
Refer to the section Measuring types and ranges (Page 13).
16
Analog input module AI 2xU ST (6ES7134-6FB00-0BA1)
Manual, 12/2015, A5E36104728-AA