Siemens Simatic ET 200SP Manual page 25

Analog input module ai 2xu st
Hide thumbs Also See for Simatic ET 200SP:
Table of Contents

Advertisement

Encoders
Connection of the signal transmitters
For voltage measurement
Errors/accuracies
Linearity error (in relation to input range), (+/-)
Temperature error (in relation to input range), (+/-) 0.005%/K
Crosstalk between inputs, min.
Repeat accuracy in settled state at 25 °C (in
relation to input range), (+/-)
Operational limit in the entire temperature range
Voltage in relation to input range, (+/-)
Basic error limit (operational limit at 25 °C)
Voltage in relation to input range, (+/-)
Interference voltage suppression for f = n x
(f1 +/-1%), f1 = interference frequency
Series-mode interference (peak of the interference
< rated value of the input range), min.
Common mode voltage, max.
Common mode interference, min.
Isochronous mode
Isochronous mode (application synchronized up to
terminal)
Interrupts/diagnostics/status information
Interrupts
Diagnostics interrupt
Limit interrupt
Diagnostics alarms
Diagnostics
Monitoring of the supply voltage
Wire break
Short-circuit
Group error
Overflow/underflow
Diagnostics indicator LED
Monitoring of the supply voltage (PWR LED)
Channel status display
For channel diagnostics
For module diagnostics
Analog input module AI 2xU ST (6ES7134-6FB00-0BA1)
Manual, 12/2015, A5E36104728-AA
Technical specifications
6.1 Technical specifications
6ES7134-6FB00-0BA1
Yes
0.01%
-50 dB
0.05%
0.5%
0.3%
70 dB
10 V
90 dB
No
Yes
No
Yes
Yes
No
Yes; with 1 to 5 V
Yes
Yes
Yes; green PWR LED
Yes; green LED
No
Yes; green/red DIAG LED