APPENDIX
(2) Precautions for replacing the conventional product (AJ65BT-
64DAV/DAI) with the AJ65SBT-62DA
In the existing system using the conventional product (AJ65BT-64DAV/DAI), the
following instructions must be noted when changing the AJ65BT-64DAV/DAI for
the AJ65SBT-62DA.
(a) Since the AJ65SBT-62DA occupies one station (the AJ65BT-64DAV/DAI
occupies two stations), the station information setting in the network
parameters must be changed.
(b) As the remote I/O signals and remote register settings are different between
the two models, the program of the conventional model cannot be utilized.
(c) Because of the differences in shape and layout between the terminal blocks,
you cannot use the terminal block of the conventional module as it is.
(d) The offset/gain setting method differs. For details, refer to Section 4.4.
(e) The ways to set the station number and transmission speed setting switches
are different. For details, refer to Section 4.3.
Appendix - 2
MELSEC-A