3 SPECIFICATION

3.6.4 Output range/HOLD/CLEAR setting (Address RWwm+3)

Example
Set 5101H when setting channel 1 to "0 to 5V" and "HOLD" and channel 2 to "User range setting
1" and "CLEAR".
b15 b14 b13 b12 b11 b10
0
(1) Make output range setting using the 8 upper bits (b8 to b15) of address RWwm+3.
Make HOLD/CLEAR setting using the 8 lower bits (b0 to b7) of address
RWwm+3.
(2) The default settings are -10 to +10V and CLEAR.
b15
to
b12
CH.2
Output range setting
0
: -10 to +10V
H
1
: 0 to 5V
H
2
: 1 to 5V
H
3
: 0 to 20mA
H
4
: 4 to 20mA
H
5
: User range setting 1 (-10 to +10V)
H
6
: User range setting 2 (0 to 5V)
H
7
: User range setting 3 (0 to 20mA)
H
1
0
1
0
0
CH.2
5
b11
to
b8
CH.1
b9
b8
b7
b6
0
1
0
0
CH.1
CH.2
1
0
3 - 15
b7
to
b4
b3
CH.2
HOLD/CLEAR setting
0
: CLEAR
H
1 to F
: HOLD
H
b5
b4
b3
b2
b1
0
0
0
0
0
CH.1
1
MELSEC-A
to
b0
CH.1
b0
1
5101
H