SETTING AND ADJUSTMENT

Selecting the power supply of the fans

WARNING! Before establishing the electrical
connection, make sure that the power supply is
off. Also ensure that it is not possible to
reconnect the power during the operation.
WARNING! In the case of a unit with ducts, the
load loss from the exhaust duct must be less than
100 Pa.
To reach the head required by the system for conditioners
with fans carrying a CE marking, the input voltage percentage
can be adjusted from the user terminal (A).
To select the voltage percentage to be applied, carry out
the following procedures:
on the user terminal press the PRG button;
using the UP or DOWN key select SERVICE MENU
and confirm using the ENTER key;
enter the password (see the envelope attached to the
manual);
using the UP or DOWN key select HARDWARE
SETTING and confirm using the ENTER key;
using the UP or DOWN key select EVAPORATING FAN
and confirm using the ENTER key;
set the amount and confirm using the ENTER key.
UNITS WITH CENTRIFUGAL FANS
Nominal fan regulation (to have the nominal airflow with ESP=20Pa)
Nominal speed @20Pa
EU4
Model
[%]
151
75
251
82
331
69
351
80
501
100
601
151
75
251
82
331
69
351
80
501
99
601
24
UNIT WITHOUT ELECTRICAL HEATERS
Minimum speed @20Pa
Eu4 +Post
EU4
[%]
[%]
75
48
82
48
69
46
80
46
100
62
75
48
82
48
69
46
80
46
99
62
A1
A2
A3
A4
In the following table the maximum pressure available
(expressed in Pa) for each voltage level of the transformer is
indicated. The values are given for the maximum air flow
(expressed in m3/h).
UNIT WITH ELECTRICAL HEATERS
Nominal speed @20Pa
Eu4 +Post
EU4
Eu4 +Post
[%]
[%]
SDAC SDWC
48
75
48
83
46
70
46
80
62
100
SUAC SUWC
48
75
48
83
46
70
46
80
62
100
Minimum speed @20Pa
EU4
Eu4 +Post
[%]
[%]
[%]
75
48
48
83
48
48
70
50
50
80
50
50
100
65
65
75
48
48
83
48
48
70
50
50
80
50
50
100
65
65
A5
A6
A7