Service - Danfoss Optyma Plus User Manual

Controller for condensing unit
Hide thumbs Also See for Optyma Plus:
Table of Contents

Advertisement

Number of LP alarms
The number of LP alarms can be read out here.
(The displayed value can be adjusted if required)
Number of discharge alarms
The number of Td alarms can be read out here.
(The displayed value can be adjusted if required)
Oil return management Speed limit
If the compressor speed exceeds this limit, a time counter will be increased. It will be
decreased if the compressor speed falls down below this limit.
Oil return management time
Limit value of the above described time counter. If the counter exceeds this limit, the
compressor speed will be raised to the Boost speed
Oil return management Boost speed
This compressor speed ensures that the oil returns to the compressor
Oil return management Boost time.
The time the compressor must operate at Boost speed.

Service

Read pressure Pc
Read temperature Taux
Status on DI1 input. On/1=closed
Status on night operation (on or off ) on =night operation
Read Superheat
Read temperature at S6 sensor
Read the compressor capacity in %
Status on DI2 input. On/1=closed
Status on relay for compressor
Status on relay for fan
Status on relay for alarm
Status on relay "Aux"
Status on relay for heating element in crankcase
Status on input DI3 (on/1 = 230 V)
Read condensing pressure in temperature
Read pressure Ps
Read suction pressure in temperature
Read ambient temperature Tamb
Read discharge temperature Td
Read suction gas temperature at Ts
Voltage on the analogue output AO1
Voltage on the analogue output AO2
10
User Guide RS8GD602 © Danfoss 2015-10
P52
LP Alarm Cnt
P53
DisAlarm Cnt
P77
ORM SpeedLim
P78
ORM Time
P79
ORM BoostSpd
P80
ORM BoostTim
Service
u01
Pc bar
u03
T_aux
u10
DI1 status
u13
NightCond
u21
Superheat SH
u36
S6 temp
u52
CompCap %
u37
DI2 status
u58
Comp Relay
u59
Fan relay
u62
Alarm relay
u63
Aux Relay
u71
CCH Relay
u87
DI3 status
U22
Tc
U23
Ps
U24
Ts
U25
T_ambient
U26
T_Discharge
U27
T_Suction
U44
AO_1 Volt
U56
AO_2 Volt
Optyma Plus
TM

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents