Alarms; Control Parameters - Danfoss Optyma Plus User Manual

Controller for condensing unit
Hide thumbs Also See for Optyma Plus:
Table of Contents

Advertisement

Max. condensing temperature (highest permitted Tc reference)
Max. discharge gas temperature Td

Alarms

Alarm time delay on signal on the DI2 input
Alarm for insufficient cooling in condenser. Set temperature difference.
Delay time for A70 alarm
Compressor
Min. ON-time
Min. OFF-time
Min. time between compressor starts
Pump down limit at which the compressor is stopped (setting 0.0 = no function)
Min. compressor speed
Start speed for compressor
Max. compressor speed
Max. compressor speed during night operation (%-value of c48)
Definition of compressor control: 0=no external start/stop; 1=switch on DI1 must start/stop
; 2=inverter compressor speed control
Time delay for high Td. The compressor will stop when time expires.
Max. pressure. Compressor stops if a higher pressure is recorded
Difference for max. pressure (c73)
Min. suction pressure Ps. Compressor stops if a lower pressure is recorded
Difference for min. suction pressure and pump down
Amplification factor Kp for compressors PI-regulation
Integration time Tn for compressors PI-regulation
Liquid Injection Offset
Liquid Injection hysterese
Compressor stop delay after Liquid injection
Desired compressor speed if the signal from the pressure transmitter Ps fails
Min On time during Low Ambient LP
Measured Tc for which the Comp min speed is raised to StartSpeed

Control parameters

Amplification factor Kp for PI-regulation
Integration time Tn for PI-regulation
Kp max for PI regulation when the measurement is far from reference
Fan
Readout of fan speed in %
Permitted change in fan speed (to a lower value) % per second.
Jog speed (speed as a % when the fan is started)
Jog speed at low temperature
Definition of fan control: 0=Off; 1=Internal control. 2=External speed control
Minimum fan speed. Decreased need will stop the fan.
Maximum fan speed
Manual control of the fan's speed. (Only when r12 is set to -1)
Real time clock
Time at which they switch to day operation
Time at which they switch to night operation
Clock - Setting of hours
Clock - Setting of minute
Clock - Setting of date
Clock - Setting of month
Clock - Setting of year
Miscellaneous
Network address
On/Off switch (Service Pin message)
IMPORTANT! o61 must be set prior to o04
(used at LON 485 only)
Access code (access to all settings)
Readout of controllers software version
14
continued
User Guide RS8GD602 © Danfoss 2015-10
Code
Min.
Max.
r83
0°C
50°C
40°C
r84
50°C
160°C
135°C
A28
0 min.
240 min.
30 min.
A70
3.0 K
20.0 K
10.0 K
A71
5 min.
240 min.
30 min.
c01
5 s
240 s
5 s
c02
3 s
240 s
30 s
c07
0 min.
30 min.
5 min.
C33
0,0 bar
15,0 bar
0,0 bar
c46
25 Hz
70 Hz
30 Hz
c47
30 Hz
70 Hz
50 Hz
c48
50 Hz
100 Hz
100 Hz
c69
50%
100%
70%
c71
0
2
1
c72
0 min.
20 min.
3 min.
c73
7.0 bar
50.0 bar
23.0 bar
c74
1.0 bar
10.0 bar
3.0 bar
c75
-0.3 bar
10.0 bar
3.0 bar
c76
0.1 bar
5.0 bar
0.7 bar
c82
3,0
30,0
20,0
c83
30 s
360 s
60 s
c88
0.1 K
20.0 K
5.0 K
c89
10.0 K
30.0 K
15.0 K
c90
0 s
10 s
3 s
c93
25 Hz
70 Hz
60 Hz
c94
0
0
120
c95
40,0
10,0
70,0
n04
1.0
20.0
7.0
n05
20
120
40
n95
5,0
50,0
20,0
F07
-
-
-
F14
1,0%
5,0%
1,0%
F15
10%
100%
40%
F16
0%
40%
10%
F17
0
2
1
F18
0%
40%
10%
F19
40%
100%
100%
F20
0%
100%
0%
t17
0 hrs
23 hrs
0
t18
0 hrs
23 hrs
0
t07
0 hrs
23 hrs
0
t08
0 min.
59 min.
0
t45
1 day
31 day
1
t46
1 mon.
12 mon.
1
t47
0 year
99 year
0
o03
0
240
0
o04
0/Off
1/On
0/Off
o05
0
100
0
o08
Fac.
Actual
Optyma Plus
TM