While observing the above guidelines, install the condensate trap as follows:
1. Connect the condensate trap inlet to the exhaust manifold drain connection by inserting
the drain port directly into the trap adaptor inlet, and then tightening the inlet thumbscrew,
as shown in Figure 2-6. The inlet features two integral O-rings to prevent leakage.
2. At the condensate trap outlet, install a 3/4" NPT nipple.
3. Connect a length of 1" diameter polypropylene hose to the trap outlet and secure with a
hose clamp.
4. Route the hose on the trap outlet to a nearby floor drain.
If a floor drain is not available, a condensate pump can be used to remove the condensate to
drain. The maximum condensate flow rate is 30 GPH. The condensate drain trap, associated
fittings and drain line must be removable for routine maintenance.
Use PVC, stainless steel, aluminum or polypropylene for condensate drain
piping (Figure 2-6). DO NOT use carbon or copper components.
COMBUTION
ANALYZER
PROBE PORT
EXHAUST
MANIFOLD
NOTE
HOUSKEEPING
PAD MUST NOT
EXTEND
UNDER THE
CONDENSATE
ASSEMBLY.
Figure 2-6: Sample Condensate Trap Installation (Right Side View)
OMM-0097_0C
GF-142
Benchmark 1500 - 2000 Boilers
CHAPTER 2 – INSTALLATION

Condensate Trap Installation

CAUTION
4" MINIMUM
(6" MAXIMUM)
EXHAUST
MANIFOLD
DRAIN PORT
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913
Ph.: 800-526-0288
TRAP INLET
INTEGRAL
ADAPTOR AND
THUMBSCREW
TOP
CONDENSATE
COVER
THUMB
TRAP (P/N 24060)
SREWS
(4 ea.)
3/4" NPT
NIPPLES
4"
HOSE
CLAMP
1" DIAM.
HOSE
T O
FLOOR
DRAIN
Page 21 of 184