4.2.1 Required Tools & Instrumentation
The following tools and instrumentation are necessary to perform combustion calibration of the
unit:
Digital Combustion Analyzer: Oxygen accuracy to ± 0.4%; Carbon Monoxide (CO) and
Nitrogen Oxide (NOx) resolution to 1PPM.
16 inch W.C. manometer or equivalent gauge and plastic tubing.
1/4 inch NPT-to-barbed fittings for use with gas supply manometer or gauge.
Small and large flat blade screwdrivers.
Tube of silicone adhesive

4.2.2 Installing Gas Supply Manometer

The gas supply manometer (or gauge) is used to monitor the gas pressure on the downstream
side of the SSOV during the Combustion Calibration procedures described in section 4.3.
The gas supply manometer is installed at the upstream and/or downstream location shown in
Figure 4-1.
MANUAL
SHUT-OFF
VALVE
Figure 4-1: BMK 1500/2000: 1/4 Inch Gas Plug Location for Combustion
Page 50 of 184
Benchmark 1500 - 2000 Boilers
CHAPTER 4 – INITIAL START-UP
TO
AIR/FUEL
VALVE
SSOV
LEAK DETECTION
BALL VALVE
Calibration
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913
Ph.: 800-526-0288
NATURAL
GAS INLET
HIGH GAS
PRESSURE
SWITCH
LOW GAS
PRESSURE
SWITCH
1/4" NPT PLUG
(Install manometer here for
Combustion Calibration)
OMM-0097_0C
GF-142

Advertisement