Appendix C: Sensor Resistance/Voltage Chart - Benchmark BMK 1500 User Manual

Table of Contents

Advertisement

APPENDIX C – SENSOR RESISTTANCE/VOLTAGE CHART

Appendix C: SENSOR RESISTANCE/VOLTAGE CHART

Temperature Sensor Resistance Voltage Chart (Balco)
OMM-0097_0C
GF-142
Benchmark 1500 - 2000 Boilers
TEMP (°F)
RES (OHMS)
-40
779.0
-30
797.5
-20
816.3
-10
835.4
0
854.8
10
874.6
20
894.7
30
915.1
40
935.9
50
956.9
60
978.3
70
1000.0
80
1022.0
90
1044.4
100
1067.0
110
1090.0
120
1113.3
130
1137.0
140
1160.9
150
1185.2
160
1209.5
170
1234.7
180
1260.0
190
1285.6
200
1311.4
210
1337.7
220
1364.2
230
1391.0
240
1418.2
250
1445.7
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913
Ph.: 800-526-0288
VOLTS*
1.93
1.96
1.99
2.02
2.05
2.07
2.10
2.12
2.15
2.17
2.20
2.23
2.25
2.27
2.30
2.32
2.34
2.36
2.39
2.41
2.43
2.45
2.47
2.50
2.52
2.54
2.56
2.58
Page 125 of 184