Operation Time Log - Benchmark BMK 1500 User Manual

Table of Contents

Advertisement

The Operation Time (T) Log can store thousands of records.
Therefore, to view the most recently logged record, enter "T"
followed by 0 (zero) and press Enter (i.e. T0 <Enter>). To view
earlier records in reverse chronological order, enter T and press
Enter. To go back 200 or 1000 records, enter T200 or T1000, etc.
and press Enter.
9.4.2

Operation Time Log

The Operation Time Log consists of a string of ASCII records stored in non-volatile memory
within the C-More Control Panel. Events such as power-up, ignition and turn-off are time
stamped. Data logged while the unit is running are run-length encoded. Data is logged or the
run-length incremented every 30 seconds. For a new run record to be logged, the fire rate or
flame strength must change by more than 5%, or the run mode must change. At steady-state,
the run-length is allowed to reach a maximum of 30 minutes before the record is logged. This
means that no more than 30 minutes of data can be lost if the unit loses power. Table 9-2
shows a sample Operation Time Log for a boiler:
The Operation Time Log can only be accessed through the RS-232 interface using a laptop or
other terminal device. Ten operation time records are displayed for each T command entry. The
operation time log can be cleared ONLY by factory authorized personnel using the Clear Log
option in the Factory menu.
Table 9-2: Sample Operation Time Log Display
Status
Off, Direct Drive
Run, Direct Drive
Run, Direct Drive
Run, Direct Drive
Run, Direct Drive
Ignition
Off, Switch
Run, Manual
Ignition
Power-up
The Sensor (S) Log can store up to 1200 records. Therefore, to
view the most recently logged record, enter "S" followed by 0
(zero) and then press Enter (i.e. S0 <Enter>). To view earlier
records in reverse chronological order, enter S and press Enter.
To go back 200 or 700 records, enter S200 or S700, etc. and
press Enter.
OMM-0097_0C
GF-142
Benchmark 1500 - 2000 Boilers
CHAPTER 9 – RS232 COMMUNICATION
NOTE
Fire Rate
Flame
0
0
38
100
31
100
35
100
29
100
0
0
0
0
40
100
0
0
0
0
NOTE
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913
Ph.: 800-526-0288
Run Length
Date
8
1/15/02
34
1/15/02
30
1/15/02
2
1/15/02
0
1/15/02
0
1/15/02
35
1/15/02
0
1/15/02
0
1/15/02
0
1/15/02
Time
2:35pm
2:27pm
1:53am
1:23pm
1:21pm
1:20pm
12:30pm
11:55am
11:55am
11:50am
Page 113 of 184