Appendix; Fault Codes - Benchmark ZB 7-28 R 28 HE Installation And Servicing Instructions

Wall mounted condensing boiler for central heating
Hide thumbs Also See for ZB 7-28 R 28 HE:
Table of Contents

Advertisement

Appendix

9
Appendix
9.1

Fault Codes

More detailed fault finding procedures are described in the Service booklet for the Engineer number 7 181 465 346.
Display
code
Description
A8
Break in communication
AC
Module not detected.
b1
Code plug not detected.
C1
Fan speed too low.
d3
Jumper 8-9 not detected.
E2
CH flow NTC sensor defective
E9
Safety temp. limiter in CH flow has tripped.
EA
Flame not detected.
F0
Internal error.
F7
Flame detected even though appliance switched off.
FA
Flame detected after gas shut off.
Fd
Reset button pressed by mistake.
P1, P2,
Please wait, initialisation in progress.
P3, P1...
Table 18
42
Remedy
Check connecting lead to programmer
Check connecting lead between TA211E/TR212E
and Heatronic
Insert code plug correctly, test and replace if neces-
sary.
Check fan lead and connector, and fan; replace as
necessary.
Connector not connected, link missing, underfloor
heating limiter tripped.
Check CH flow NTC sensor and connecting lead.
Check system pressure, check safety temp. limiters,
check pump operation, check fuse on pcb, bleed
appliance.
Is gas cock turned on? Check gas supply pressure,
power supply, igniter electrode and lead, ionisation
sensing electrode and lead, flue duct and CO
Check electrical connector contacts, programmer
interface module ignition leads are not loose; replace
pcb if necessary.
Check electrode assembly, dry pcb. Flue clear?
Check gas valve and wiring to gas valve. Clean con-
densation trap and check electrode assembly. Flue
clear?
Press reset button again
24 V fuse blown. Replace fuse.
level.
2
6 720 611 443 GB (05.04)