8. Remove the top front covers of all cabinets.
Press and release the handle latch at the bottom of the cover and
then lift the cover up and off the cabinet.
9. Install the remaining ground straps between each cabinet (see
Figure 27).
10. Reinstall the top front covers removed in Step 8.
Hang the top edge of the cover on the cabinet first, then lower the
bottom edge and snap into place.
11. Continue to "Operation" on page 39 to start up the UPS.
NOTE After UPS startup, ensure maximum battery runtime by configuring the UPS for the
correct number of EBMs (see page 49).
Front Ground Strap
Figure 27. Front Ground Strap Installation (2-High Cabinets Shown)
Eaton 9155 Parallel UPS (8–15 kVA) User's Guide
EXTENDED BATTERY MODULE INSTALLATION
S
164201592 Rev D www.eaton.com/powerquality