Table 21. Maximum shock specifications
Maximum shock
Operating
Storage
Table 22. Maximum altitude specifications
Maximum altitude
Operating
Storage
Table 23. Operating temperature de-rating specifications
Operating temperature de-rating
Up to 35°C (95°F)
35°C to 40°C (95°F to 104°F)
40°C to 45°C (104°F to 113°F)
Related Links
Expanded operating temperature

Particulate and gaseous contamination specifications

The following table defines the limitations that help avoid any equipment damage or failure from
particulates and gaseous contamination. If the levels of particulates or gaseous pollution exceed the
specified limitations and result in equipment damage or failure, you may need to rectify the
environmental conditions. Re-mediation of environmental conditions is the responsibility of the
customer.
Table 24. Particulate contamination specifications
Particulate contamination
Air filtration
Specifications
Six consecutively executed shock pulses in the
positive and negative x, y, and z axes of 40 G for up
to 2.3 ms.
Six consecutively executed shock pulses in the
positive and negative x, y, and z axes (one pulse on
each side of the system) of 71 G for up to 2 ms.
Specifications
3048 m (10,000 ft)
12,000 m (39,370 ft)
Specifications
Maximum temperature is reduced by 1°C/300 m
(1°F/547 ft) above 950 m (3,117 ft).
Maximum temperature is reduced by 1°C/175 m
(1°F/319 ft) above 950 m (3,117 ft).
Maximum temperature is reduced by 1°C/125 m
(1°F/228 ft) above 950 m (3,117 ft).
Specifications
Data center air filtration as defined by ISO Class 8
per ISO 14644-1 with a 95% upper confidence
limit.
29