EasiCool™

Technical Data

Operating Limits
Indoor Air Temperature
Indoor RH%
Outdoor Temperature
0
Nominal Design Operating Condition 24°C Dry Bulb 45% RH
IMPORTANT
58
EasiCool Technical Manual 7525389 V1.8.0_05_2016
+18°C to +28°C
+40% to +55% (Based upon 24°C Dry Bulb)
-20°C to +41°C
5
10
15
18
Fan Power Input (Fan Gain) must be added to the room load to establish full gross cooling
capacity requirements.
Fan Power Input can be found in the mechanical data sections.
Fan Power Input is taken at the operating conditions based on 25Pa ESP.
Precision Air Conditioning
20
25
30
35
28
Dry Bulb Temperature (°C)
Moisture Content
Operating Band
40