EasiCool™ EZRE
Downflow and Upflow - Precision Air Conditioning
Direct Expansion
6kW - 60kW
Technical Manual
FM00542
EMS52086

Advertisement

Table of Contents
loading

Summary of Contents for AIREDALE EasiCool

  • Page 1 EasiCool™ EZRE Downflow and Upflow - Precision Air Conditioning Direct Expansion 6kW - 60kW Technical Manual FM00542 EMS52086...
  • Page 2: Warranty, Commissioning & Maintenance

    Airedale Ltd endeavours to ensure that the information in this document is correct and fairly stated, but none of the statements are to be relied upon as a statement or representation of fact. Airedale Ltd does not accept liability for any error or omission, or for any reliance placed on the information contained in this document.
  • Page 3: Health And Safety

    Airedale recommends that personal protective equipment is used whilst installing, maintaining and commissioning equipment. Refrigerant Warning The Airedale Easicool unit uses R410A refrigerant which requires careful attention to proper storage and handling procedures. Use only manifold gauge sets designed for use with R410A refrigerant. Use only refrigerant recovery units and cylinders designed for high pressure refrigerants.
  • Page 4: Environmental Considerations

    Precision Air Conditioning Environmental Considerations Freeze Protection Airedale recommends the following actions to help protect the unit during low temperature operation. This also includes the units subject to low ambient temperatures. Units with supply water temperatures below +5°C Glycol is recommended when a supply water temperature of +5°C or below is required or when static water can be exposed to freezing temperatures.
  • Page 5: Table Of Contents

    Refrigerant Charging Guide Packaged Unit Pre-Charged Refrigerant Volumes Oil Charging Guide Refrigerant Pipesizing Guide - X Type Downflow Ethylene Glycol Correction Factors - WX Models Water Detection Tape Installation System Pipework Schematic Interconnecting Wiring pLAN Termination EasiCool Technical Manual 7525389 V1.8.0_05_2016...
  • Page 6 V35WX - V45WX V50WX2 - V60WX2 Hydronic Data Condenser Waterside Pressure Drop Hydronic Data Low Pressure Hot Water Fan Data Calculating Total Static Pressure Fan Speed Data EZRE Direct Expansion 400V 50Hz (-0) After Sales EasiCool Technical Manual 7525389 V1.8.0_05_2016...
  • Page 7: Specifiers Guide

    Full function units provide full control of temperature, humidification, de-humidification, heating and filtration. The modular design of the EasiCool allows grouping of differing model types and capacities to be installed side by side. The flexibility of this type of installation provides for multi-circuit functionality.
  • Page 8: Unit Overview

    Unit Overview Downflow Cooling Coil Air Filters Control Panel Heating Humidifier ●Electric ●Low Pressure Hot Water ●Hot Gas Scroll Compressors Fan Motor Assembly Upflow Fan Motor Assembly Control Panel Cooling Coil Air Filters Scroll Compressors Humidifier EasiCool Technical Manual 7525389 V1.8.0_05_2016...
  • Page 9: Construction

    Sizes 6 - 26 Dependent upon model type, components such as the expansion valve, compressor, humidifier and sight glass are contained within an acoustically lined enclosure to provide both ease of maintenance and to minimise sound emission. EasiCool Technical Manual 7525389 V1.8.0_05_2016...
  • Page 10: Refrigeration Components

    The cooling coil is mounted over a full width stainless steel condensate tray. Factory pressure tested to 45 Barg. X Models Only Sweat copper pipe for brazed connection as standard. EasiCool Technical Manual 7525389 V1.8.0_05_2016...
  • Page 11 • Sight Glass • Head Pressure Control • Filter Drier • Low Pressure Switch • High Pressure Switch • Liquid Line Pressure Transducer • Full operating charge of R410A • Bleed valve • Binder points EasiCool Technical Manual 7525389 V1.8.0_05_2016...
  • Page 12 The valve will allow cooling water to flow to the condenser, to bypass the condenser, or to allow water flow to both condenser and by-pass line in order to maintain correct refrigerant head pressure. The head pressure can be monitored via the display keypad. EasiCool Technical Manual 7525389 V1.8.0_05_2016...
  • Page 13 Precise temperature control is obtained as a result of modulating the refrigerant flow in the evaporator by throttling the valve on the suction line. Maximum Minimum Fully Closed Fully Open Capacity @ 24°C / 45% RH return air conditions EER @ 24°C / 45% RH return air conditions EasiCool Technical Manual 7525389 V1.8.0_05_2016...
  • Page 14 Evaporation Key: (1) Cooling Cycle @ 22°C ambient with a conventional TEV fitted. (2) Cooling cycle @ 22°C ambient, demonstrating a typical EEV condensing temperature taking full advantage of lower ambient air temperatures (below 35°C). EasiCool Technical Manual 7525389 V1.8.0_05_2016...
  • Page 15: Airflow Components

    – – ● ● Return Air Grille ○ ○ ○ ○ G4 Return Door Air Filter ● ○ – Standard Feature Optional Feature Not Available Model Dependant on selected units with AC fans as standard. EasiCool Technical Manual 7525389 V1.8.0_05_2016...
  • Page 16 Filters Pleated disposable panel filters in a rigid frame. Conform to BS EN 779-G4. Access and removal from unit front. As standard the microprocessor provides an alarm following a preset run time limit being exceeded. EasiCool Technical Manual 7525389 V1.8.0_05_2016...
  • Page 17 The following illustration shows a comparison of the typical power input required by each method. Airflow EC (Electronically Commutated) Fan Speed Control Regulated (VR) Fan Speed Control EasiCool Technical Manual 7525389 V1.8.0_05_2016...
  • Page 18: Electrical Components

    A phase sequence relay shall be avaliable for units containing 3 phase scroll compressors, to prevent possible damage by running the compressor the wrong direction. If Phase Rotation Protection and an Energy Manager unit are both required, the Energy Manager IMPORTANT will require the addition of a Field Card, please contact Airedale. EasiCool Technical Manual 7525389 V1.8.0_05_2016...
  • Page 19: Heating And Humidification

    Frost protection is fitted to prevent freezing of the low pressure hot water coil assembly. Proportional heating control is provided by a factory fitted 3 port, raise/lower type, modulating valve. Access to the Right hand side of the unit is required to set up the regulating valve EasiCool Technical Manual 7525389 V1.8.0_05_2016...
  • Page 20 As standard the humidifier is fitted with the standard conductivity cylinder which covers the majority of water supplies. Where the water conductivity is known, please specify at order. For further details please contact Airedale. The supply water pressure to the humidifier assembly must be between 1 - 8 barg.
  • Page 21: Humidification

    Optimised Lifetime The life span of the Airedale humidification system shall be optimised by the inclusion of a water conductivity sensor into the bottle feed. This sensor shal determine the conductivity level of the supply water and by using an algorithm embedded in the software, determines the frequency that the bottle should be drained.
  • Page 22: Controls

    The default screen shows the unit status and room condition (°C/RH %) without the need for interrogation and an easy to navigate menu structure for further interrogation and adjustment. Standard Icons Fan Operating De-humidi cation Cooling - Up to 2 Stages Humidi cation - Variable Heating - Up to 3 Stages EasiCool Technical Manual 7525389 V1.8.0_05_2016...
  • Page 23 Modbus/Carel BMS Connection The Airedale controllers shall be able to communicate directly using the Modbus® protocol. The Modbus® card shall be a small PCB (60mm x 30mm), which can be plugged into the controller to provide it with the following protocol support Modbus®...
  • Page 24 Flood • Phase Failure • Critical • Non-critical • Airflow failure ( • Compressor failure (Optional on DX units only) ( • Electric Heating Overheat cut-out ( • Humidifier alarm (Full Function units only) ( EasiCool Technical Manual 7525389 V1.8.0_05_2016...
  • Page 25 The control system integrity can be maintained by restricting access with a password PIN number. CAUTION IMPORTANT: To change the PIN number, please contact Airedale at time of order with the preferred 4 digit number. Remote On/Off Terminals for interlocking are provided to enable or disable the unit remotely.
  • Page 26: Optional Extras

    The display keypad can be upgraded to include audible alerts. BMS Interface Card Enables Controlled units to be interfaced with most BMS, factory fitted, please contact Airedale. A wide range of protocols can be accommodated through the use of interface devices. Available as a standard option are: ModBus/Jbus, Carel and Trend.
  • Page 27: General Features

    Straight and ‘L’ shaped duct extensions up to a height of 1350 mm constructed and finished to match the unit are available. For extensions greater than 1350 mm, please contact Airedale. Height; please specify at order. Services Side Access Gland Plate As standard services can be routed through the gland plate in the base of the units.
  • Page 28 Units shall be supplied complete with additional LAT corner protection and cross braces to afford extra transit protection. Sterling board heat treated man made material shall be used (including pallet) to comply with phytosanity import regulations (please contact Airedale for this option). Optional Extras General...
  • Page 29 It is MOST IMPORTANT that CAUTION the steam distribution pipe is not damaged or kinked at any time to avoid the risk of unacceptably high pressure building up in the electrode bottle. EasiCool Technical Manual 7525389 V1.8.0_05_2016...
  • Page 30: Sound Measurement Method

    Within the conditioned space, sound from in-room ducted discharge air grilles and other equipment will contribute to the overall sound level and should therefore be considered as part of sound calculations. Specialist acoustic advice is recommended for noise critical applications. (1)Return Air (2)Case Breakout (3)Discharge Air Return Air Case Breakout Discharge Air EasiCool Technical Manual 7525389 V1.8.0_05_2016...
  • Page 31 Precision Air Conditioning EasiCool™ Notes EasiCool Technical Manual 7525389 V1.8.0_05_2016...
  • Page 32: Dimensional & Installation Data

    Standard forward airflow direction. Optional reverse airflow direction. Optional gland plate and panel for side services access via the right side of unit. For services details contact Airedale. Base mains cable entry. Standard base gland plate entry for refrigeration/water services. For services details contact Airedale.
  • Page 33 Standard forward airflow direction. Optional reverse airflow direction. Optional gland plate and panel for side services access via the right side of unit. For services details contact Airedale. Base mains cable entry. Standard base gland plate entry for refrigeration/water services. For services details contact Airedale.
  • Page 34 Standard forward airflow direction. Optional reverse airflow direction. Optional gland plate and panel for side services access via the right side of unit. For services details contact Airedale. Base mains cable entry. Standard base gland plate entry for refrigeration/water services. For services details contact Airedale.
  • Page 35 Standard forward airflow direction. Optional reverse airflow direction. Optional gland plate and panel for side services access via the right side of unit. For services details contact Airedale. Base mains cable entry. Standard base gland plate entry for refrigeration/water services. For services details contact Airedale.
  • Page 36 V28 - V60 X/X2/WX/WX2 1310 X/X2/WX/WX2 1310 X/X2/WX/WX2 1685 X/X2/WX/WX2 1685 X2/WX2 1685 X2/WX2 3020 X2/WX2 3020 X2/WX2 3020 1 25 mm flange required to return air duct work, supplied by others. 2 M6 fixings holes required. EasiCool Technical Manual 7525389 V1.8.0_05_2016...
  • Page 37: Positioning

    When placing the unit on the floorstand ensure appropriate air seal is used to prevent leakage at the join. CAUTION It is also important to place all locking bolts in place to secure the unit to its base (EC fan floorstands only). EasiCool Technical Manual 7525389 V1.8.0_05_2016...
  • Page 38: Minimum Unit Clearances

    Shown with optional open floor stand. Shaded area indicates minimum service and maintenance requirements. Dimension C denotes recommended minimum/maximum floorstand height, refer to Airedale for special applications, please specify at order. Min = Threaded foot at minimum extension. Max = Threaded foot at maximum extension.
  • Page 39 (5) Optional base return. (6) Optional rear return. (7) SERVICES SIDE ACCESS GLAND PLATE, OPTIONAL POSITION; ensure appropriate clearance is available to the base of the RHS of the unit if this option is selected. EasiCool Technical Manual 7525389 V1.8.0_05_2016...
  • Page 40: Weights

    Weights quoted for units fitted with the optional Backward Curved EC fan motor exclude the cooling fan weight within the unit cabinet (AHU). Machine weight includes a refrigerant charge / Operating weight includes calculated water volume. EasiCool Technical Manual 7525389 V1.8.0_05_2016...
  • Page 41 Weights quoted for units fitted with the standard forward curved EC fan motor include the cooling fan weight within the unit cabinet (AHU). Machine weight includes a refrigerant charge / Operating weight includes calculated water volume.. EasiCool Technical Manual 7525389 V1.8.0_05_2016...
  • Page 42: Refrigeration Pipework

    When the load increases the velocity of the refrigerant ensures that oil carries up both tubes. Care must be taken in sizing double riser systems. CAUTION EasiCool Technical Manual 7525389 V1.8.0_05_2016...
  • Page 43 Liquid Line If the system is configured with the EasiCool higher than the condenser unit it may be required to increase the degree of sub cooling to prevent flashing gas occurring in the liquid line. This flashing is due to excess pressure drop caused by the static head of liquid refrigerant and can results in poor operation of the evaporator and expansion device.
  • Page 44: Refrigerant Charging Guide

    CR65 V31X-EZRE CR50 CR65 V31X2-EZRE CR50 CR65 V35X-EZRE CR50 CR65 V35X2-EZRE CR50 CR65 V40X-EZRE CR65 CR80 V40X2-EZRE CR65 CR80 V45X2-EZRE CR80 CR105 16.7 V50X2-EZRE CR80 CR105 16.7 V55X2-EZRE CR80 CR105 16.7 V60X2-EZRE CR80 CR105 16.7 EasiCool Technical Manual 7525389 V1.8.0_05_2016...
  • Page 45: Packaged Unit Pre-Charged Refrigerant Volumes

    The following table shows the refrigerant charge / metre for the liquid line, using R410A and assuming a liquid line temperature of 40°C. kg/m Liquid Line (m) 0.05 3/8” 0.09 1/2” 0.15 5/8” 0.21 3/4” 0.30 7/8” 0.53 1 1/8” EasiCool Technical Manual 7525389 V1.8.0_05_2016...
  • Page 46 = 0.5 kg. (As calculated from above) System Refrigerant = 1.0 kg Charge = LR + IR + OR = 2.7 kg = 4.2 kg / Circuit Where: SR = 0.5 + 1.0 + 2.7 Therefore EasiCool Technical Manual 7525389 V1.8.0_05_2016...
  • Page 47 (30.99 bar) = 52°C (from refrigerant tables) Sub Cooling Required = 54.4 - 52 = 2.4 °C =Condensing temperature - Saturation temperature Therefore liquid sub cooling required to prevent liquid flashing = 2.4 °C EasiCool Technical Manual 7525389 V1.8.0_05_2016...
  • Page 48: Oil Charging Guide

    OT = (RC / 200) - (OC x 0.09) RC = OT + (OC x 0.09 x 200) RC = 0 + (1.2x 0.09 x 200) RC = 21.6 kg EasiCool Technical Manual 7525389 V1.8.0_05_2016...
  • Page 49: Refrigerant Pipesizing Guide - X Type Downflow

    Precision Air Conditioning EasiCool™ Refrigerant Pipesizing Guide - X Type Downflow Pipe lengths calculated for Indoor unit with Airedale Outdoor Unit match. Indoor Unit Equivalent Pipe Lengths with R410A Connection Size 0-15m 15-40m Indoor Outdoor Discharge Discharge Liquid Discharge Liquid...
  • Page 50 EasiCool™ Precision Air Conditioning Refrigerant Pipesizing Guide - X Type Upflow Pipe lengths calculated for Indoor unit with Airedale Outdoor Unit match. Indoor Unit Equivalent Pipe Lengths with R410A Connection Size 0-15m 15-40m Indoor Outdoor Discharge Discharge Liquid Discharge Liquid...
  • Page 51: Ethylene Glycol Correction Factors - Wx Models

    EasiCool™ Ethylene Glycol Correction Factors - WX Models For conditions outside those quoted, please refer to Airedale. The Use of Glycol Glycol is recommended when a supply water temperature of +5°C or below is required or when static water can be exposed to freezing temperatures.
  • Page 52: Water Detection Tape Installation

    If in doubt, it is recommended to clean the fl oor with a mild detergent. For further information, please refer to Airedale’s Technical Bulletin and Loose Part Instruction Manual. EasiCool Technical Manual 7525389 V1.8.0_05_2016...
  • Page 53 Precision Air Conditioning EasiCool™ EasiCool Technical Manual 7525389 V1.8.0_05_2016...
  • Page 54: System Pipework Schematic

    50X2 - 60X2) Temperature Sensor - Discharge Gas (Sizes 28X - 45X & 50X2 - 60X2) MATCHED OUTDOOR CONDENSER Shut Off Valve (Supplied loose) - Optional with Outdoor Units Liquid Line Condenser Coil & Fan EasiCool Technical Manual 7525389 V1.8.0_05_2016...
  • Page 55 Suction Throttle Valve; not available with HGRH and not available with Tandem Scroll units (Sizes 20X2 - 26X2 & 50X2 - 60X2) Temperature Sensor - Discharge Gas (Sizes 28X - 45X & 50X2 - 60X2) EasiCool Technical Manual 7525389 V1.8.0_05_2016...
  • Page 56: Interconnecting Wiring

    Remote On/Off   INDOOR UNIT 24Vac   Rx-Tx-   Rx+Tx+  Network Connections (Inward connection)    INDOOR UNIT Rx-Tx-   Rx+Tx+  Network Connections (Outward connection)    EasiCool Technical Manual 7525389 V1.8.0_05_2016...
  • Page 57: Plan Termination

    The plugged termination ensures that the connections are made simultaneously. Failure to attach the cables this way may cause damage to the controller. Customer Side RxTx - RxTx + RxTx - RxTx + Panel Side EasiCool Technical Manual 7525389 V1.8.0_05_2016...
  • Page 58: Technical Data

    Fan Power Input (Fan Gain) must be added to the room load to establish full gross cooling capacity requirements. IMPORTANT Fan Power Input can be found in the mechanical data sections. Fan Power Input is taken at the operating conditions based on 25Pa ESP. EasiCool Technical Manual 7525389 V1.8.0_05_2016...
  • Page 59: Technical Data Downflow Units X Type

    Indoor Air Temperature +18°C to +28°C Indoor RH% +40% to +55% (based upon 24°C Dry Bulb) Outdoor Temperature -20°C to +41°C TC = Total Cooling SC = Sensible Cooling (1) All data quoted is gross EasiCool Technical Manual 7525389 V1.8.0_05_2016...
  • Page 60 Indoor Air Temperature +18°C to +28°C Indoor RH% +40% to +55% (based upon 24°C Dry Bulb) Outdoor Temperature -20°C to +41°C TC = Total Cooling SC = Sensible Cooling (1) All data quoted is gross EasiCool Technical Manual 7525389 V1.8.0_05_2016...
  • Page 61 Indoor Air Temperature +18°C to +28°C Indoor RH% +40% to +55% (based upon 24°C Dry Bulb) Outdoor Temperature -20°C to +41°C TC = Total Cooling SC = Sensible Cooling (1) All data quoted is gross EasiCool Technical Manual 7525389 V1.8.0_05_2016...
  • Page 62 Indoor Air Temperature +18°C to +28°C Indoor RH% +40% to +55% (based upon 24°C Dry Bulb) Outdoor Temperature -20°C to +41°C TC = Total Cooling SC = Sensible Cooling (1) All data quoted is gross EasiCool Technical Manual 7525389 V1.8.0_05_2016...
  • Page 63: Noise Data

    Power Sound @ 3m Pressure (1) dB(A) is the overall sound level, measured on the A scale (2) All sound data measured at nominal conditions, Discharge Air, Return air and case breakout is sound power. EasiCool Technical Manual 7525389 V1.8.0_05_2016...
  • Page 64 Power Sound @ 3m Pressure (1) dB(A) is the overall sound level, measured on the A scale (2) All sound data measured at nominal conditions, Discharge Air, Return air and case breakout is sound power. EasiCool Technical Manual 7525389 V1.8.0_05_2016...
  • Page 65 Precision Air Conditioning EasiCool™ EasiCool Technical Manual 7525389 V1.8.0_05_2016...
  • Page 66: Df6X - Df10X

    For refrigerant charges, refer to Unit Refrigerant Charge (kg/Circuit). Based on air temperature of 15.5°C leaving the evaporator coil. Based upon low pressure hot water 82°C inlet / 71°C outlet. Air on 20°C. Refer to Low Pressure Hot Water. EasiCool Technical Manual 7525389 V1.8.0_05_2016...
  • Page 67 Values given for full function units (incl. electric heating, humidification and matched condenser) at 7°C evaporating and 54.4°C condensing with standard forward curved fan motors, for optional data, please contact Airedale. Values given for Cooling only units (incl. Compressor, evaporator fan and matched condenser) at 7°C evaporating and 54.4°C condensing, for optional data, please contact Airedale.
  • Page 68: Df13X - Df17X

    For refrigerant charges, refer to Unit Refrigerant Charge (kg/Circuit). Based on air temperature of 15.5°C leaving the evaporator coil. Low Pressure Hot Water. Based upon low pressure hot water 82°C inlet / 71°C outlet. Air on 20°C. Refer to EasiCool Technical Manual 7525389 V1.8.0_05_2016...
  • Page 69 Values given for full function units (incl. electric heating, humidification and matched condenser) at 7°C evaporating and 54.4°C condensing with standard forward curved fan motors, for optional data, please contact Airedale. Values given for Cooling only units (incl. Compressor, evaporator fan and matched condenser) at 7°C evaporating and 54.4°C condensing, for optional data, please contact Airedale.
  • Page 70: Df20X2 - Df26X2

    For refrigerant charges, refer to Unit Refrigerant Charge (kg/Circuit). Based on air temperature of 15.5°C leaving the evaporator coil. Based upon low pressure hot water 82°C inlet / 71°C outlet. Air on 20°C. Refer to Low Pressure Hot Water. EasiCool Technical Manual 7525389 V1.8.0_05_2016...
  • Page 71 Values given for full function units (incl. electric heating, humidification and matched condenser) at 7°C evaporating and 54.4°C condensing with standard forward curved fan motors, for optional data, please contact Airedale. Values given for Cooling only units (incl. Compressor, evaporator fan and matched condenser) at 7°C evaporating and 54.4°C condensing, for optional data, please contact Airedale.
  • Page 72: Df28X - Df31X

    1775 / 2165 Speed @ 25Pa / Maximum ESP Maximum ESP 1.53 1.53 Fan Power Input (Fan Gain) Copper Tube/Aluminium Fin Low Pressure Hot Water 21.3 22.7 Capacity Gross 0.48 0.51 Water Flow (Nominal) LPHW Connection Sizes EasiCool Technical Manual 7525389 V1.8.0_05_2016...
  • Page 73 Values given for full function units (incl. electric heating, humidification and matched condenser) at 7°C evaporating and 54.4°C condensing with standard forward curved fan motors, for optional data, please contact Airedale. Values given for Cooling only units (incl. Compressor, evaporator fan and matched condenser) at 7°C evaporating and 54.4°C condensing, for optional data, please contact Airedale.
  • Page 74: Df35X - Df45X

    Speed @ 25Pa / Maximum ESP Maximum ESP 2.78 3.78 3.78 Fan Power Input (Fan Gain) Low Pressure Hot Water Copper Tube/Aluminium Fin 30.0 31.5 31.5 Capacity Gross 0.67 0.70 0.70 Water Flow (Nominal) LPHW Connection Sizes EasiCool Technical Manual 7525389 V1.8.0_05_2016...
  • Page 75 Values given for full function units (incl. electric heating, humidification and matched condenser) at 7°C evaporating and 54.4°C condensing with standard forward curved fan motors, for optional data, please contact Airedale. Values given for Cooling only units (incl. Compressor, evaporator fan and matched condenser) at 7°C evaporating and 54.4°C condensing, for optional data, please contact Airedale.
  • Page 76: Df50X2 - Df60X2

    Speed @ 25Pa / Maximum ESP Maximum ESP 3.78 3.78 3.78 Fan Power Input (Fan Gain) Copper Tube/Aluminium Fin Low Pressure Hot Water 38.3 38.3 39.8 Capacity Gross 0.85 0.85 0.89 Water Flow (Nominal) LPHW Connection Sizes EasiCool Technical Manual 7525389 V1.8.0_05_2016...
  • Page 77 Values given for full function units (incl. electric heating, humidification and matched condenser) at 7°C evaporating and 54.4°C condensing with standard forward curved fan motors, for optional data, please contact Airedale. Values given for Cooling only units (incl. Compressor, evaporator fan and matched condenser) at 7°C evaporating and 54.4°C condensing, for optional data, please contact Airedale.
  • Page 78: Hydronic Data Low Pressure Hot Water

    ∆P = Pressure Drop in kPa, Q = Water Flow Rate in l/s and M =       Fluid 100% water, for glycol use, refer to Ethylene Glycol Correction Factors. EasiCool Technical Manual 7525389 V1.8.0_05_2016...
  • Page 79 Precision Air Conditioning EasiCool™ Notes EasiCool Technical Manual 7525389 V1.8.0_05_2016...
  • Page 80: Technical Data Upflow Units X Type

    28.4 27.2 26.5 Operating Limits Indoor Air Temperature +18°C to +28°C Indoor RH% +40% to +55% Outdoor Temperature -20°C to +41°C TC = Total Cooling SC = Sensible Cooling (1) All data quoted is gross EasiCool Technical Manual 7525389 V1.8.0_05_2016...
  • Page 81 66.2 62.8 62.8 Operating Limits Indoor Air Temperature +18°C to +28°C Indoor RH% +40% to +55% Outdoor Temperature -20°C to +41°C TC = Total Cooling SC = Sensible Cooling (1) All data quoted is gross EasiCool Technical Manual 7525389 V1.8.0_05_2016...
  • Page 82 27.3 26.7 25.5 Operating Limits Indoor Air Temperature +18°C to +28°C Indoor RH% +40% to +55% Outdoor Temperature -20°C to +41°C TC = Total Cooling SC = Sensible Cooling (1) All data quoted is gross EasiCool Technical Manual 7525389 V1.8.0_05_2016...
  • Page 83 64.4 60.9 60.9 Operating Limits Indoor Air Temperature +18°C to +28°C Indoor RH% +40% to +55% Outdoor Temperature -20°C to +41°C TC = Total Cooling SC = Sensible Cooling (1) All data quoted is gross EasiCool Technical Manual 7525389 V1.8.0_05_2016...
  • Page 84: Noise Data

    Power Sound @ 3m Pressure (1) dB(A) is the overall sound level, measured on the A scale (2) All sound data measured at nominal conditions, Discharge Air, Return air and case breakout is sound power. EasiCool Technical Manual 7525389 V1.8.0_05_2016...
  • Page 85 Power Sound @ 3m Pressure (1) dB(A) is the overall sound level, measured on the A scale (2) All sound data measured at nominal conditions, Discharge Air, Return air and case breakout is sound power. EasiCool Technical Manual 7525389 V1.8.0_05_2016...
  • Page 86: V6X - V10X

    For refrigerant charges, refer to Unit Refrigerant Charge (kg/Circuit). Based on air temperature of 15.5°C leaving the evaporator coil. Based upon low pressure hot water 82°C inlet / 71°C outlet. Air on 20°C. Refer to Low Pressure Hot Water. EasiCool Technical Manual 7525389 V1.8.0_05_2016...
  • Page 87 Values given for full function units (incl. electric heating, humidification and matched condenser) at 7°C evaporating and 54.4°C condensing with standard forward curved fan motors, for optional data, please contact Airedale. Values given for Cooling only units (incl. Compressor, evaporator fan and matched condenser) at 7°C evaporating and 54.4°C condensing, for optional data, please contact Airedale.
  • Page 88: V13X - V17X

    For refrigerant charges, refer to Unit Refrigerant Charge (kg/Circuit). Based on air temperature of 15.5°C leaving the evaporator coil. Based upon low pressure hot water 82°C inlet / 71°C outlet. Air on 20°C. Refer to Low Pressure Hot Water. EasiCool Technical Manual 7525389 V1.8.0_05_2016...
  • Page 89 Values given for full function units (incl. electric heating, humidification and matched condenser) at 7°C evaporating and 54.4°C condensing with standard forward curved fan motors, for optional data, please contact Airedale. Values given for Cooling only units (incl. Compressor, evaporator fan and matched condenser) at 7°C evaporating and 54.4°C condensing, for optional data, please contact Airedale.
  • Page 90: V20X2 - V26X2

    For refrigerant charges, refer to Unit Refrigerant Charge (kg/Circuit). Based on air temperature of 15.5°C leaving the evaporator coil. Based upon low pressure hot water 82°C inlet / 71°C outlet. Air on 20°C. Refer to Low Pressure Hot Water. EasiCool Technical Manual 7525389 V1.8.0_05_2016...
  • Page 91 Values given for full function units (incl. electric heating, humidification and matched condenser) at 7°C evaporating and 54.4°C condensing with standard forward curved fan motors, for optional data, please contact Airedale. Values given for Cooling only units (incl. Compressor, evaporator fan and matched condenser) at 7°C evaporating and 54.4°C condensing, for optional data, please contact Airedale.
  • Page 92: V28X- V31X2

    1935 / 2165 Maximum ESP Fan Power Input (Fan Gain) 2.02 2.02 3.02 3.02 Low Pressure Hot Water Copper Tube/Aluminium Fin Capacity Gross 21.7 21.7 23.2 23.2 Water Flow (Nominal) 0.48 0.48 0.52 0.52 LPHW Connection Sizes EasiCool Technical Manual 7525389 V1.8.0_05_2016...
  • Page 93 Values given for full function units (incl. electric heating, humidification and matched condenser) at 7°C evaporating and 54.4°C condensing with standard forward curved fan motors, for optional data, please contact Airedale. Values given for Cooling only units (incl. Compressor, evaporator fan and matched condenser) at 7°C evaporating and 54.4°C condensing, for optional data, please contact Airedale.
  • Page 94: V35X - V45X2

    3.08 3.08 4.24 4.24 4.24 Fan Power Input (Fan Gain) Copper Tube/Aluminium Fin Low Pressure Hot Water 29.9 29.9 31.5 31.5 31.5 Capacity Gross 0.67 0.67 0.70 0.70 0.70 Water Flow (Nominal) LPHW Connection Sizes EasiCool Technical Manual 7525389 V1.8.0_05_2016...
  • Page 95 Values given for full function units (incl. electric heating, humidification and matched condenser) at 7°C evaporating and 54.4°C condensing with standard forward curved fan motors, for optional data, please contact Airedale. Values given for Cooling only units (incl. Compressor, evaporator fan and matched condenser) at 7°C evaporating and 54.4°C condensing, for optional data, please contact Airedale.
  • Page 96: V50X2 - V60X2

    Speed @ 25Pa / Maximum ESP Maximum ESP 4.18 4.18 4.18 Fan Power Input (Fan Gain) Copper Tube/Aluminium Fin Low Pressure Hot Water 37.7 37.7 39.2 Capacity Gross 0.84 0.84 0.87 Water Flow (Nominal) LPHW Connection Sizes EasiCool Technical Manual 7525389 V1.8.0_05_2016...
  • Page 97 Values given for full function units (incl. electric heating, humidification and matched condenser) at 7°C evaporating and 54.4°C condensing with standard forward curved fan motors, for optional data, please contact Airedale. Values given for Cooling only units (incl. Compressor, evaporator fan and matched condenser) at 7°C evaporating and 54.4°C condensing, for optional data, please contact Airedale.
  • Page 98: Hydronic Data Low Pressure Hot Water

    ∆P = Pressure Drop in kPa, Q = Water Flow Rate in l/s and M =       Fluid 100% water, for glycol use, refer to Ethylene Glycol Correction Factors. EasiCool Technical Manual 7525389 V1.8.0_05_2016...
  • Page 99 Precision Air Conditioning EasiCool™ Notes EasiCool Technical Manual 7525389 V1.8.0_05_2016...
  • Page 100: Technical Data Downflow Units Wx Type

    (1) All data quoted is gross (2) Interpolate for water temperatures between those quoted, do not extrapolate (3) Water flow rate (l/s) = THR/(4.19*ΔT) at 100% Water; for glycol use refer to Ethylene Glycol Correction Factors section EasiCool Technical Manual 7525389 V1.8.0_05_2016...
  • Page 101 (1) All data quoted is gross (2) Interpolate for water temperatures between those quoted, do not extrapolate (3) Water flow rate (l/s) = THR/(4.19*ΔT) at 100% Water; for glycol use refer to Ethylene Glycol Correction Factors section EasiCool Technical Manual 7525389 V1.8.0_05_2016...
  • Page 102: Noise Data

    Power Sound @ 3m Pressure (1) dB(A) is the overall sound level, measured on the A scale (2) All sound data measured at nominal conditions, Discharge Air, Return air and case breakout is sound power. EasiCool Technical Manual 7525389 V1.8.0_05_2016...
  • Page 103 Power Sound @ 3m Pressure (1) dB(A) is the overall sound level, measured on the A scale (2) All sound data measured at nominal conditions, Discharge Air, Return air and case breakout is sound power. EasiCool Technical Manual 7525389 V1.8.0_05_2016...
  • Page 104: Df6Wx - Df10Wx

    Based on air temperature of 15.5°C leaving the evaporator coil. Based upon low pressure hot water 82°C inlet / 71°C outlet. Air on 20°C. Refer to Low Pressure Hot Water (Optional Extra) - X & WX Models. EasiCool Technical Manual 7525389 V1.8.0_05_2016...
  • Page 105 Values given for full function units (incl. electric heating, humidification and matched condenser) at 7°C evaporating and 54.4°C condensing with standard forward curved fan motors, for optional data, please contact Airedale. Values given for Cooling only units (incl. Compressor, evaporator fan and matched condenser) at 7°C evaporating and 54.4°C condensing, for optional data, please contact Airedale.
  • Page 106: Df13Wx - Df17Wx

    Based on air temperature of 15.5°C leaving the evaporator coil. Based upon low pressure hot water 82°C inlet / 71°C outlet. Air on 20°C. Refer to Low Pressure Hot Water (Optional Extra) - X & WX Models. EasiCool Technical Manual 7525389 V1.8.0_05_2016...
  • Page 107 Values given for full function units (incl. electric heating, humidification and matched condenser) at 7°C evaporating and 54.4°C condensing with standard forward curved fan motors, for optional data, please contact Airedale. Values given for Cooling only units (incl. Compressor, evaporator fan and matched condenser) at 7°C evaporating and 54.4°C condensing, for optional data, please contact Airedale.
  • Page 108: Df20Wx2 - Df26Wx2

    Based on air temperature of 15.5°C leaving the evaporator coil. Based upon low pressure hot water 82°C inlet / 71°C outlet. Air on 20°C. Refer to Low Pressure Hot Water (Optional Extra) - X & WX Models. EasiCool Technical Manual 7525389 V1.8.0_05_2016...
  • Page 109 Values given for full function units (incl. electric heating, humidification and matched condenser) at 7°C evaporating and 54.4°C condensing with standard forward curved fan motors, for optional data, please contact Airedale. Values given for Cooling only units (incl. Compressor, evaporator fan and matched condenser) at 7°C evaporating and 54.4°C condensing, for optional data, please contact Airedale.
  • Page 110: Df28Wx - Df31Wx

    1.70 2.50 Fan Power Input (Fan Gain) Low Pressure Hot Water Copper Tube/Aluminium Fin 21.3 22.7 Capacity Gross 0.48 0.51 Water Flow (Nominal) LPHW Connection Sizes Threaded Connection 1 1/4 1 1/4 Brass Male Taper EasiCool Technical Manual 7525389 V1.8.0_05_2016...
  • Page 111 Values given for full function units (incl. electric heating, humidification and matched condenser) at 7°C evaporating and 54.4°C condensing with standard forward curved fan motors, for optional data, please contact Airedale. Values given for Cooling only units (incl. Compressor, evaporator fan and matched condenser) at 7°C evaporating and 54.4°C condensing, for optional data, please contact Airedale.
  • Page 112: Df35Wx - Df45Wx

    Fan Power Input (Fan Gain) Low Pressure Hot Water Copper Tube/Aluminium Fin 30.0 31.5 31.5 Capacity Gross 0.67 0.70 0.70 Water Flow (Nominal) LPHW Connection Sizes Threaded Connection 1 1/4 1 1/4 1 1/2 Brass Male Taper EasiCool Technical Manual 7525389 V1.8.0_05_2016...
  • Page 113 Values given for full function units (incl. electric heating, humidification and matched condenser) at 7°C evaporating and 54.4°C condensing with standard forward curved fan motors, for optional data, please contact Airedale. Values given for Cooling only units (incl. Compressor, evaporator fan and matched condenser) at 7°C evaporating and 54.4°C condensing, for optional data, please contact Airedale.
  • Page 114: Df50Wx2 - Df60Wx2

    Fan Power Input (Fan Gain) Low Pressure Hot Water Copper Tube/Aluminium Fin 38.30 38.30 39.8 Capacity Gross 0.85 0.85 0.89 Water Flow (Nominal) LPHW Connection Sizes Threaded Connection 1 1/2 1 1/2 1 1/2 Brass Male Taper EasiCool Technical Manual 7525389 V1.8.0_05_2016...
  • Page 115 Values given for full function units (incl. electric heating, humidification and matched condenser) at 7°C evaporating and 54.4°C condensing with standard forward curved fan motors, for optional data, please contact Airedale. Values given for Cooling only units (incl. Compressor, evaporator fan and matched condenser) at 7°C evaporating and 54.4°C condensing, for optional data, please contact Airedale.
  • Page 116: Hydronic Data Condenser Waterside Pressure Drop

    ∆P = Pressure Drop in kPa, Q = Water Flow Rate in l/s and M =       Fluid 100% water, for glycol use, refer to Ethylene Glycol Correction Factors. EasiCool Technical Manual 7525389 V1.8.0_05_2016...
  • Page 117: Hydronic Data Low Pressure Hot Water

    ∆P = Pressure Drop in kPa, Q = Water Flow Rate in l/s and M =       Fluid 100% water, for glycol use, refer to Ethylene Glycol Correction Factors. EasiCool Technical Manual 7525389 V1.8.0_05_2016...
  • Page 118: Technical Data Upflow Units Wx Type

    (1) All data quoted is gross (2) Interpolate for water temperatures between those quoted, do not extrapolate (3) Water flow rate (l/s) = THR/(4.19*ΔT) at 100% Water; for glycol use refer to Ethylene Glycol Correction Factors section EasiCool Technical Manual 7525389 V1.8.0_05_2016...
  • Page 119 (1) All data quoted is gross (2) Interpolate for water temperatures between those quoted, do not extrapolate (3) Water flow rate (l/s) = THR/(4.19*ΔT) at 100% Water; for glycol use refer to Ethylene Glycol Correction Factors section EasiCool Technical Manual 7525389 V1.8.0_05_2016...
  • Page 120: Noise Data

    Power Sound @ 3m Pressure (1) dB(A) is the overall sound level, measured on the A scale (2) All sound data measured at nominal conditions, Discharge Air, Return air and case breakout is sound power. EasiCool Technical Manual 7525389 V1.8.0_05_2016...
  • Page 121 Power Sound @ 3m Pressure (1) dB(A) is the overall sound level, measured on the A scale (2) All sound data measured at nominal conditions, Discharge Air, Return air and case breakout is sound power. EasiCool Technical Manual 7525389 V1.8.0_05_2016...
  • Page 122: V6Wx - V10Wx

    Based on air temperature of 15.5°C leaving the evaporator coil. Based upon low pressure hot water 82°C inlet / 71°C outlet. Air on 20°C. Refer to Low Pressure Hot Water (Optional Extra) - X & WX Models. EasiCool Technical Manual 7525389 V1.8.0_05_2016...
  • Page 123 Values given for full function units (incl. electric heating, humidification and matched condenser) at 7°C evaporating and 54.4°C condensing with standard forward curved fan motors, for optional data, please contact Airedale. Values given for Cooling only units (incl. Compressor, evaporator fan and matched condenser) at 7°C evaporating and 54.4°C condensing, for optional data, please contact Airedale.
  • Page 124: V13Wx - V17Wx

    Based on air temperature of 15.5°C leaving the evaporator coil. Based upon low pressure hot water 82°C inlet / 71°C outlet. Air on 20°C. Refer to Low Pressure Hot Water (Optional Extra) - X & WX Models. EasiCool Technical Manual 7525389 V1.8.0_05_2016...
  • Page 125 Values given for full function units (incl. electric heating, humidification and matched condenser) at 7°C evaporating and 54.4°C condensing with standard forward curved fan motors, for optional data, please contact Airedale. Values given for Cooling only units (incl. Compressor, evaporator fan and matched condenser) at 7°C evaporating and 54.4°C condensing, for optional data, please contact Airedale.
  • Page 126: V20Wx2 - V26Wx2

    Based on air temperature of 15.5°C leaving the evaporator coil. Based upon low pressure hot water 82°C inlet / 71°C outlet. Air on 20°C. Refer to Low Pressure Hot Water (Optional Extra) - X & WX Models. EasiCool Technical Manual 7525389 V1.8.0_05_2016...
  • Page 127 Values given for full function units (incl. electric heating, humidification and matched condenser) at 7°C evaporating and 54.4°C condensing with standard forward curved fan motors, for optional data, please contact Airedale. Values given for Cooling only units (incl. Compressor, evaporator fan and matched condenser) at 7°C evaporating and 54.4°C condensing, for optional data, please contact Airedale.
  • Page 128: V28Wx - V31Wx2

    Low Pressure Hot Water Copper Tube/Aluminium Fin 21.70 21.70 23.2 23.2 Capacity Gross 0.48 0.48 0.52 0.52 Water Flow (Nominal) LPHW Connection Sizes Threaded Connection 1 1/4 1 1/4 1 1/4 1 1/4 Brass Male Taper EasiCool Technical Manual 7525389 V1.8.0_05_2016...
  • Page 129 Values given for full function units (incl. electric heating, humidification and matched condenser) at 7°C evaporating and 54.4°C condensing with standard forward curved fan motors, for optional data, please contact Airedale. Values given for Cooling only units (incl. Compressor, evaporator fan and matched condenser) at 7°C evaporating and 54.4°C condensing, for optional data, please contact Airedale.
  • Page 130: V35Wx - V45Wx

    Copper Tube/Aluminium Fin 29.90 29.90 31.5 31.5 31.5 Capacity Gross 0.67 0.67 0.70 0.70 0.70 Water Flow (Nominal) LPHW Connection Sizes Threaded Connection 1 1/4 1 1/4 1 1/4 1 1/4 1 1/4 Brass Male Taper EasiCool Technical Manual 7525389 V1.8.0_05_2016...
  • Page 131 Values given for full function units (incl. electric heating, humidification and matched condenser) at 7°C evaporating and 54.4°C condensing with standard forward curved fan motors, for optional data, please contact Airedale. Values given for Cooling only units (incl. Compressor, evaporator fan and matched condenser) at 7°C evaporating and 54.4°C condensing, for optional data, please contact Airedale.
  • Page 132: V50Wx2 - V60Wx2

    Fan Power Input (Fan Gain) Low Pressure Hot Water Copper Tube/Aluminium Fin 37.7 37.7 39.2 Capacity Gross 0.84 0.84 0.87 Water Flow (Nominal) LPHW Connection Sizes Threaded Connection 1 1/2 1 1/2 1 1/2 Brass Male Taper EasiCool Technical Manual 7525389 V1.8.0_05_2016...
  • Page 133 Values given for full function units (incl. electric heating, humidification and matched condenser) at 7°C evaporating and 54.4°C condensing with standard forward curved fan motors, for optional data, please contact Airedale. Values given for Cooling only units (incl. Compressor, evaporator fan and matched condenser) at 7°C evaporating and 54.4°C condensing, for optional data, please contact Airedale.
  • Page 134: Hydronic Data Condenser Waterside Pressure Drop

    ∆P = Pressure Drop in kPa, Q = Water Flow Rate in l/s and M =       Fluid 100% water, for glycol use, refer to Ethylene Glycol Correction Factors. EasiCool Technical Manual 7525389 V1.8.0_05_2016...
  • Page 135: Hydronic Data Low Pressure Hot Water

    ∆P = Pressure Drop in kPa, Q = Water Flow Rate in l/s and M =       Fluid 100% water, for glycol use, refer to Ethylene Glycol Correction Factors. EasiCool Technical Manual 7525389 V1.8.0_05_2016...
  • Page 136: Fan Data

    V 50 - 60 1510 rpm 1250 RPM 1000 RPM 750 RPM 2.00 2.50 3.00 3.50 4.00 4.50 5.00 5.50 6.00 AirFlow [m Internal Static Pressure + External Static Pressure = Total Static Pressure e.g. 575+85 = 660 EasiCool Technical Manual 7525389 V1.8.0_05_2016...
  • Page 137: Fan Speed Data

    V28 -60 - EC Forward Fan Curve V28 - 31 V50 - 60 V35 - 45 0.00 0.50 1.00 1.50 2.00 2.50 3.00 3.50 4.00 4.50 5.00 5.50 6.00 AirFlow [m System Curve Unit Standard Airflow EasiCool Technical Manual 7525389 V1.8.0_05_2016...
  • Page 138: Ezre Direct Expansion 400V 50Hz (-0)

    V 6- 8 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00 1.10 Airflow [m DF/V10 - 50Hz DF/V 10 - 50Hz DF 10 V 10 0.40 0.50 0.60 0.70 0.80 0.90 1.00 1.10 1.20 Airflow [m EasiCool Technical Manual 7525389 V1.8.0_05_2016...
  • Page 139 1.10 1.20 1.30 Airflow [m DF/V15 - 17 - 50Hz DF/V 15-17 - 50Hz DF 15 - 17 V 15 - 17 0.70 0.80 0.90 1.00 1.10 1.20 1.30 1.40 1.50 1.60 1.70 Airflow [m EasiCool Technical Manual 7525389 V1.8.0_05_2016...
  • Page 140 DF28 - 60 - EC Forward Fan Curve DF 28-60 - EC Forward Fan Curve DF50 - 60 DF28 - 31 DF35 - 45 0.00 0.50 1.00 1.50 2.00 2.50 3.00 3.50 4.00 4.50 5.00 5.50 6.00 AirFlow [m EasiCool Technical Manual 7525389 V1.8.0_05_2016...
  • Page 141 6.00 AirFlow [m DF6 - 10 - EC Backward Fan Curve DF6 -10 EC Backward Fan Curve 0.00 0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00 1.10 1.20 1.30 1.40 Air Volume [m EasiCool Technical Manual 7525389 V1.8.0_05_2016...
  • Page 142 DF20 - 26 - EC Backward Fan Curve DF20 - 26 EC Backward Fan Curve 1100 1000 1.00 1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00 2.10 2.20 2.30 2.40 Air Volume [m EasiCool Technical Manual 7525389 V1.8.0_05_2016...
  • Page 143 AirFlow [m DF35 - 45 - Backward Fan Curve DF35 -45 Backward Fan Curve 1000 2150 RPM DF 35- 45 1900 RPM 1500 RPM 1100 RPM 1.50 2.00 2.50 3.00 3.50 4.00 4.50 AirFlow [m EasiCool Technical Manual 7525389 V1.8.0_05_2016...
  • Page 144 EZRE Direct Expansion 400V 50Hz (-0) DF50 - 60 - Backward Fan Curve DF50 -60 Backward Fan Curve 1510 RPM DF 50-60 1250 RPM 1000 RPM 750 RPM 2.00 2.50 3.00 3.50 4.00 4.50 5.00 5.50 6.00 AirFlow [m EasiCool Technical Manual 7525389 V1.8.0_05_2016...
  • Page 145: After Sales

    All Airedale products or parts (non consumable) supplied for installation within the UK mainland and commissioned by an Airedale engineer, carry a full Parts & Labour warranty for a period of 12 months from the date of commissioning or 18 months from the date of despatch, whichever is the sooner.
  • Page 146 Head Offi ce Airedale International Air Conditioning Ltd Leeds Road Rawdon Leeds LS19 6JY Tel: +44 (0) 113 2391000 Fax:+44 (0) 113 2507219 E-mail enquiries@airedale.com Web www.airedale.com TM_EASICOOL_EZRE_7525389_1.8.0_05_2016...