AIREDALE EasiCool Technical Manual page 11

Table of Contents

Advertisement

Precision Air Conditioning
Compressor
Compressor(s) are mounted on the base via the use of vibration isolators.
Each compressor is designed for use with R410A refrigerant.
Thermal Protection
Single Compressor
Tandem Compressors
Standard Feature
Optional Feature – Not Available
Tandem Compressors
Comprising of 2 scroll type compressors linked together by refrigerant pipework to
one common circuit.
Tandem compressors provide variable control of the system performance by
activating individual compressors as required. Multiple steps of unloading allow
external load demands to be met with greater precision, eliminating unnecessary
temperature and humidity variations. Consequently, system efficiency and reliability
are much improved by extending major component working hours.
X and WX Models
Utilise a single hermetic scroll compressor fitted as standard with:
Thermal motor protection internal or external (dependent upon model size)
High temperature discharge protection
X2 and WX2 Models
Utilise a tandem hermetic scroll compressor set, to provide 2 stages of control, fitted
as standard with:
Thermal motor protection internal or external (dependent upon model size)
High temperature discharge protection
Sight glass on common equalisation line.
Refrigeration
Each refrigeration circuit features as standard:
X Type
Externally Equalised Thermostatic
Expansion Valve (TEV)
Sight Glass
Head Pressure Control
Filter Drier
WX Type
Externally equalised thermostatic expansion valve (TEV)
Sight Glass
Head Pressure Control
Filter Drier
Low Pressure Switch
High Pressure Switch
Liquid Line Pressure Transducer
Full operating charge of R410A
Bleed valve
Binder points
X
X2
WX
Low Pressure Switch
High pressure Switch
Liquid Line Pressure Transducer
Holding Charge of Inert Gas
WX2
EasiCool Technical Manual 7525389 V1.8.0_05_2016