Airedale Ltd. endeavours to ensure that the information in this document is correct and fairly stated, but none of the statements are to be relied upon as a statement or representation of fact. Airedale Ltd. does not accept liability for any error or omission, or for any reliance placed on the information contained in this document.
IMPORTANT The information contained in this manual is critical to the correct operation and maintenance of the unit and should be read by all persons responsible for the installation, commissioning and maintenance of this Airedale unit. Safety The equipment has been designed and manufactured to meet international safety standards but, like any mechanical/ electrical equipment, care must be taken if you are to obtain the best results.
** Based on the maximum allowable water temperature. ROHS COMPLIANCE Under the EU Directives, Airedale International Air Conditioning Ltd. hereby declares that Artus products are RoHS compliant according to the definitions and restrictions given by the Directive 2011/65/EU of The European Parliament and of the Council of June 8, 2011 on the restriction of the use of certain hazardous substances in electrical and electronic equipment (EEE).
Page 5
Comfort ARTUS™ Ecodesign Data Item Cooling Capacity (Sensible) (1) (2) (3) Prated, c Cooling Capacity (Latent) (1) (2) (3) Prated, c Heating Capacity (65/55°C) (4) Prated, h Heating Capacity (45/35°C) (4) Prated, h Total electric power input at 140 l/s 0.015 0.015 0.015...
ARTUS™ Comfort Contents Customer Services Health and Safety Environmental Policy Specification Introduction Nomenclature Unit Overview Construction Airflow Electrical Waterside Controls Quick Selection Quick Selection Procedure Quick Selection - Section A - Capacity Quick Selection - Section B - Waterside Pressure Drop Quick Selection - Section C - Acoustics Quick Selection - Section D - Air Throw Quick Selection - Section E - Fan Power Technical Data Operating Limits Performance Data - High Water Flow Rate Coil (>0.1l/s) Performance Data - Low Water Flow Rate Coil (<0.1l/s) Mechanical and Electrical Data Installation...
Comfort ARTUS™ Specification Introduction The Artus Low energy fan coil unit is designed for both cooling and heating with no system ductwork. The unit is self contained with all controls, valves and auxiliary equipment required for operation. The Artus is a versatile, flexible solution designed with ease of installation, commissioning and maintenance in mind.
Camouflage ● Micro Perforation Pattern (SAS D1522). ● 0.7mm Polyester Powder Coated Zintec. ● Free Area 22%. ● Other options are available, contact Airedale. Fascia Sizes Available in sizes: 572 x 572mm (10mm border, to fit 24mm Ceiling Systems). 581 x 581mm (10mm border, to fit 15mm Ceiling Systems).
ARTUS™ Comfort Airflow Fan & Motor Assembly The fan is encased in a bespoke plastic shroud which has an aerodynamic profile increasing the efficiency of the fan assembly inside the unit. The plastic shroud is made from 30% glass filled nylon minimising the weight of the hinged door assembly.
Comfort ARTUS™ Electrical Electrical connections are located conveniently on a external face of the unit. Item Description 230V/1PH/50Hz Mains Incoming Connector* BACnet MSTP Connection (optional) KNX Display Connection to Room Sensor BACnet Port X1 RJ45 (optional) ...
Page 12
ARTUS™ Comfort Electrical A control box is located internally within the unit with a dedicated panel housing all electrical components. All wiring is numbered and conforms to European standards. Units are powered from a 230V/1PH/50Hz power supply making them suitable for domestic installation. ...
Option 1. 2 pipe, 2 port PIC valve single mode of heat transfer (cooling or heating) The first option available from Airedale is a single coil with an integrated PIC valve. Option 2. 4 pipe, 2 coils segregated cooling and heating with 2 port PIC valves The second option is segregated coils for cooling and heating.
Page 14
ARTUS™ Comfort Unit Terminations 2 Pipe, 2 Port PIC Valve Cooling Mode Cooling Outlet Return Return Air Cooling Inlet Supply 2 Pipe, 2 Port PIC Valve Heating Mode Heating Outlet Return Return Air Heating Inlet Supply 2 Port PIC Motorised Valve Bleed Valve ARTUS™...
Page 15
Comfort ARTUS™ Unit Terminations 4 Pipe, 2 Coil Cooling and Heating Segregated Coils Cooling Inlet Supply Return Air Cooling Outlet Return Heating Inlet Supply Return Air Heating Outlet Return 2 Port PIC Motorised Valve Bleed Valve ARTUS™ Technical Manual 9690348 v3_04_2020...
Page 16
ARTUS™ Comfort Unit Terminations 4 Pipe, 1 Coil Cooling and Heating Changeover Coil Cooling Mode Return Cooling Outlet Heating Outlet Return Air Supply Cooling Inlet Heating Inlet Heating Mode Cooling Outlet Return Heating Outlet Return Air Cooling Inlet Supply Heating Inlet 2 Port PIC Motorised Valve Bleed Valve 3 Port Thermic Valve...
Page 17
Comfort ARTUS™ Water Control Valve 2 Port Pressure Independent Control Valve (PIC Valve). 0-10V. Constant flow is achieved by use of the PIC valve. The PIC valve operates on a principle of equal percentage. ● Excellent valve authority and control - not affected by system pressure fluctuations. ●...
Page 18
ARTUS™ Comfort Condensate Pump The condensate pump fitted to the unit shall be a rotary diaphragm pump with the following features: ● Rotary diaphragm “GyRok” technology. ● Antibacterial tubing open to atmosphere via an air vent in the reservoir – this inhibits the growth of bacteria inside the tubing.
Ethernet ports on IP variants. In the case of BACnet IP, to minimise installation time, two RJ45 sockets on the side of the Artus are provided for line topologies. To build larger networks for Artus units, Airedale recommends use of Ethernet switch on each segment.
Page 20
ARTUS™ Comfort Controls Overview Unlike traditional fan coils, the control system and valve arrangement are fully integrated into each Artus as standard. The Artus controller is a native BACnet device and is fully tested, and certified by the BACnet association. Features Thermal Control –...
Page 21
Comfort ARTUS™ Controls Room Operator Unit (optional) The Room Operator Unit offers touch sensitive keys, an internal NTC sensor, segmented backlit display and is powered directly via the KNX bus. The Room Operator Unit has an integral sensor to measure room temperature. When networked with an Artus, it controls to an average of the room temperature taken from the operator unit and the return air temperature of each respective unit.
Page 22
ARTUS™ Comfort Room Operator Display Green Leaf Function Energy efficiency is indicated by a leaf icon. The icon is either Green or Red. A green leaf signals to the occupant that the Artus is operating at its most optimised energy efficient mode. A red leaf indicates that setpoint parameters have changed locally (a manual override).
(Section B, Graph 8) (Section B, Graph 10) (Section B, Graph 9) (Section B, Graph 11) The quick selection graphs are based on nominal conditions of 27°C/ 46% Return air. If different selections are required, please contact Airedale. ARTUS™ Technical Manual 9690348 v3_04_2020...
Page 24
ARTUS™ Comfort Quick Selection Quick Selection Procedure This flow chart is designed to guide you through the selection process for Artus, selecting the unit coil type and supply airflow based on a desired heating effect. Heating How many Coils? 2 Coils 1 Coil Select the supply airflow against the heating effect based on...
Comfort ARTUS™ Quick Selection - Section A - Capacity Graph 1 - High Flow Coil Changeover: Supply Airflow vs. Cooling Effect 3.50 3.00 2.50 2.00 6/9°C Water Temps 8/11°C Water Temps 1.50 10/13°C Water Temps 14/17°C Water Temps 1.00 Data based upon return air of 0.50 27°C/ 46% RH.
Page 26
ARTUS™ Comfort Quick Selection - Section A - Capacity Graph 2 - Low Flow Coil Changeover: Supply Airflow vs. Cooling Effect 3.50 3.00 2.50 2.00 6/12°C Water Temps 8/14°C Water Temps 1.50 10/16°C Water Temps 14/20°C Water Temps 1.00 Data based upon return air of 0.50 27°C/ 46% RH.
Page 27
Comfort ARTUS™ Quick Selection - Section A - Capacity Graph 3 - High Flow Coil Changeover: Supply Airflow vs. Heating Effect 4.50 4.00 3.50 3.00 2.50 50/40°C Water Temps 45/35°C Water Temps 2.00 40/35°C Water Temps 1.50 35/30°C Water Temps 1.00 Data based upon return air of 20°C.
Page 28
ARTUS™ Comfort Quick Selection - Section A - Capacity Graph 4 - Low Flow Coil Changeover: Supply Airflow vs. Heating Effect 4.00 3.50 3.00 2.50 45/35°C Water Temps 2.00 40/35°C Water Temps 35/30°C Water Temps 1.50 30/25°C Water Temps 1.00 Data based upon return air 0.50 of 20°C.
Page 29
Comfort ARTUS™ Quick Selection Section A - Capacity Graph 5 - High Flow Coil Segregated: Supply Airflow vs. Cooling Effect 3.50 3.00 2.50 2.00 6/9°C Water Temps 8/11°C Water Temps 1.50 10/13°C Water Temps 14/17°C Water Temps 1.00 Data based upon return air of 0.50 27°C/ 46% RH.
Page 30
ARTUS™ Comfort Quick Selection Section A - Capacity Graph 6 - Low Flow Coil Segregated: Supply Airflow vs. Cooling Effect 3.50 3.00 2.50 2.00 6/9°C Water Temps 8/11°C Water Temps 1.50 10/13°C Water Temps 14/17°C Water Temps 1.00 Data based upon return air of 0.50 27°C/ 46% RH.
Page 31
Comfort ARTUS™ Quick Selection - Section A - Capacity Graph 7 - Heating Coil Segregated: Supply Airflow vs. Heating Effect 1.60 1.40 1.20 1.00 82/71°C Water Temps 0.80 70/60°C Water Temps 60/50°C Water Temps 0.60 50/40°C Water Temps 0.40 Data based upon return air 0.20 of 20°C.
ARTUS™ Comfort Quick Selection - Section C - Acoustics Noise performance is critical to satisfactory selection of air conditioning equipment. The components within Artus were selected to give an acceptable noise level at ‘typical’ cooling effects and supply airflow rates. For a given set of chilled water temperatures, the cooling effect depends on the supply airflow and to a good approximation they are directly proportional.
Page 35
Comfort ARTUS™ Assessment by an Acoustic Consultant For maximum accuracy the assessment of the acoustics is best undertaken by an acoustic consultant. Many factors need to be taken into account, including the noise generated by each Artus unit, the effect of multiple Artus units, the distance between noise source and observer, room reverberation and the extent of absorption by surfaces.
Page 36
ARTUS™ Comfort Quick Selection - Section C - Acoustics Assessment without an Acoustic Consultant For projects that do not have an acoustic consultant the following estimations are provided. This is a less precise approach than using an acoustic consultant. These estimates are for a number of typical case study scenarios. The NR figures have been calculated for each case by an acoustic consultant and the input data is shown.
Page 37
Comfort ARTUS™ Quick Selection - Section C - Acoustics Commercial Office with False Ceiling Mid- Cooling Supply Zone Max kW Ceiling Sound frequency load Description Zone Type airflow, Calc NR Finishes Dimensions each Insulation reverberation time In ceiling, Carpet, Metal open plan, 6m x 4.5m plaster walls,...
Page 38
ARTUS™ Comfort Quick Selection - Section C - Acoustics Commercial Office without False Ceiling, Exposed Services Cooling Mid-frequency Zone Max kW Supply Ceiling Sound Description Zone Type load Calc NR Finishes reverberation Dimensions each airflow, l/s Insulation W/m2 time Carpet, Exposed, plaster open plan,...
Page 39
Comfort ARTUS™ Quick Selection - Section C - Acoustics Residence / hotel - Living room / bedroom Cooling Supply Mid-frequency Max kW Ceiling Sound load Caption airflow, Calc NR Finishes reverberation each Insulation time W/m2 Residential Floor: oak matt lacquered Solid ‘penthouse’, engineered planks + loose...
Comfort ARTUS™ Technical Data Performance Data - High Water Flow Rate Coil (>0.1l/s) Cooling Nominal Airflow 140l/s Combined Coil Chilled Water Inlet and Outlet Temperatures - 3K Water ∆t - Nominal Airflow 140l/s Model Air On 6 / 9 °C 7 / 10 °C 8 / 11 °C 9 / 12 °C...
Page 44
ARTUS™ Comfort Technical Data Performance Data - High Water Flow Rate Coil (>0.1l/s) Heating Nominal Airflow 140l/s Combined Coil Heated Water Inlet and Outlet Temperatures - 5K Water ∆t - Nominal Airflow 140l/s Model Air On 50 / 45 °C 45 / 40 °C 40 / 35 °C 35 / 30 °C...
Comfort ARTUS™ Technical Data Performance Data - Low Water Flow Rate Coil (<0.1l/s) Cooling Nominal Airflow 140l/s Combined Coil Chilled Water Inlet and Outlet Temperatures - 6K Water ∆t - Nominal Airflow 140l/s Model Air On 6 / 12 °C 7 / 13 °C 8 / 14 °C 9 / 15 °C...
Page 46
ARTUS™ Comfort Technical Data Performance Data - Low Water Flow Rate Coil (<0.1l/s) Heating Nominal Airflow 140/s Combined Coil Heated Water Inlet and Outlet Temperatures - 5K Water ∆t - Nominal Airflow 140l/s Model Air On 45 / 40 °C 40 / 35 °C 35 / 30 °C 30 / 25 °C...
Comfort ARTUS™ Technical Data Mechanical and Electrical Data Notes Units Capacity Nom Cooling (Gross) 2.86 2.67 2.86 2.84 2.66 2.84 Nom Heating (Gross) 1.43 0.23 1.57 0.23 Nom Heating (Gross) 7.05 1.19 7.23 1.19 Fan Power Input (Fan Gain) 12.7 14.8 12.7 12.7...
ARTUS™ Comfort Installation Installation should be completed in the following order: 1. Unpack the unit and check the contents against the list below. 2. Mount and level the unit, ensuring that the stated clearances and airflow requirements are observed. Check the condensate drain is in the correct position and that the hose is free from damage or kinks.
Comfort ARTUS™ Installation Unpacking the Ceiling Raft Step - Carry and place the box in a safe area for unpacking. It is advised that 2 people perform this operation or a trolley is used. Step - Open the box from top face as shown.
ARTUS™ Comfort Installation Pipework Termination Positions 2 Pipe 4 Pipe 1 Coil Changeover CW IN HW OUT CW OUT HW IN 4 Pipe 2 Coils Segregated CW IN HW OUT HW IN CW OUT ARTUS™ Technical Manual 9690348 v3_04_2020...
ARTUS™ Comfort Installation Clearance and Airflow Requirements - Ceiling Unit 600mm 600mm RETURN SUPPLY RETURN RETURN SUPPLY SUPPLY Image Displaying Cooling Mode 600mm clearance is required around the unit to ensure correct, efficient operation. This is for both airflow and mechanical services.
Comfort ARTUS™ Installation Clearance and Airflow Requirements - Exposed Unit The exposed Artus requires the same clearance of 600mm around the unit for airflow and mechanical services. Additional clearance is required below the unit for removal of the raft. The raft is removed / opened by pivoting on one edge.
ARTUS™ Comfort Installation X, Y, Z, Adjustable Installation Frame (supplied by others) The Artus hybrid fan coil unit has been designed to fit in a low profile ceiling void. The unit is 206mm tall. To accommodate a mounting frame which facilities adjustment of the unit relative to the ceiling tiles, at least a further 85mm will need to be available to facilitate a two tier unistrut arrangement for around 60mm of adjustment.
Comfort ARTUS™ Installation Ceiling Integration Options View on Rear of Unit 24mm T-Bar Ceiling Arrangement View on side of unit 2 EQUAL GAP 572 FASCIA PLATE 2 EQUAL GAP 24 T-Bar 24 T-Bar 15mm T-Bar Ceiling Arrangement View on side of unit 2 GAP 581 FASCIA PLATE 2 GAP...
ARTUS™ Comfort Installation Ceiling Raft Once the Artus is installed and levelled, the following procedure can be carried out to mount the raft. Step - Before the lock nuts on the installation frame are tightened, the raft mounting bracket is to be fitted. ...
Page 57
Comfort ARTUS™ Installation Ceiling Raft Step - Level the raft mounting frame using the M6 bolt. Ensure the unit and raft is level within ±1°. = ±1° Step - Lift the decorative raft at an angle and hook it on the mounting frame. ...
ARTUS™ Comfort Installation Condensate Drain During operation in cooling mode, the unit removes moisture and lowers humidity from the air. This moisture must be removed to ensure that the drain tray does not overflow. The condensate pump outlet must be connected to the building drainage system as per the diagram below. Gradient 1/50 -1/100 Fall Max 800mm 6mm ID braided hose is recommended for the condensate drain hose.
Comfort ARTUS™ Return Air Temperature Sensor Return Air Temperature Sensor (located behind filter). Cooling Coil Bleed Valve Access (2 Coil units only). Bleeding Air Out of the Coil An air bleed is located at the top of the coil. This is accessed by dropping the fascia (single coil units) and through the access hole on the outside of the case (dual coil units).
ARTUS™ Comfort Installation Interconnecting Wiring Electrical Connections ● A fused and isolated electrical supply of the appropriate phase, frequency and voltage should be installed by the customer. ● As standard the product is for an electrical supply of 230V, 1 Phase, 50Hz. ●...
ARTUS™ Comfort Installation Water Termination Electrical power is needed at the unit to drive the valve gear during waterside commissioning. CAUTION Electrical installation and commissioning must be fully completed before the waterside installation and commissioning can take place. Do not remove actuators during pipework installation and flushing. Actuators need to be powered CAUTION for commissioning.
Recommended Pipework (External to Unit) This diagram shows the valid install for a 2 pipe Artus unit; another manifold set would be required for a 4 pipe Artus unit. Please contact Airedale for more information. Fixed ori ce ow measurement device...
Page 64
2 pipe heating only 2 pipe cooling only Recommended Pipework Installation - 4 Pipe Cooling and Heating Changeover Coil Plate heat Airedale (or third party) air-cooled chiller exchanger 2 pipe cooling only 4 pipe heating and cooling Glycol Circuit...
Airedale do not offer any commissioning services for the Artus. Mechanical commissioning, including water side balancing, must be completed by others before Airedale or other third party CAUTION Siemens Solution Partners configure the Artus(s) for master/slave operation, room operator units, BMS integration and so forth.
Page 68
ARTUS™ Comfort Commissioning Pressure Independent Control Valve (PICV) The valve is factory set to position 9. Flow adjustment To set the selected flow, rotate the dial on the valve to the desired position. Line up the desired preset position to the indicator mark on the valve body.
Thermic Valve Commissioning Steps The Airedale valve override plugs must be used during commissioning to simulate a heating/cooling demand. This is important as - unlike fan coil units without this feature - the valve heads should not be removed during commissioning and must instead be driven to the correct heating or cooling position.
ARTUS™ ARTUS™ Comfort Comfort Maintenance Accessibility The design of the system allows servicing to be carried out readily and easily. Lowering the fascia enables access and allows replacement of certain parts. Electrical The equipment has been designed and manufactured to meet international safety standards but, like any mechanical/ electrical equipment, care must be taken if you are to obtain the best results.
Page 71
The filters required to be changed are supplied in a kit from Airedale. The kit comprises of two short and one long filter. ARTUS™ Technical Manual 9690348 v3_04_2020...
ARTUS™ ARTUS™ Comfort Comfort Maintenance Opening the Unit Locate the latch side of the unit which can be identified by the 2 larger 6mm holes in the fascia panel. A 4mm Allen key should be offered up to the unit through the 6mm perforated holes in the fascia panel and on to the hex socket on the latch housing.
ARTUS™ ARTUS™ Comfort Comfort Maintenance Drain Tray Removal Remove push fit hose from drip tray spigots either side prior to removing tray (be aware the drip tray could contain condensate). Engage snap barbs at either end of drip tray to remove from coil end plates. Manipulate the tray from the front locating lugs to drop the drip tray out from the unit / ceiling void.
(W x L) (mm) (24mm T-bar) (15mm T-bar) (no T-bar) – – 572 x 572 – – 581 x 581 – – 596 x 596 – Airedale Recommended Optional Installation Option Not Available ARTUS™ Technical Manual 9690348 v3_04_2020...
Page 76
ARTUS™ ARTUS™ Comfort Comfort Maintenance Fascia Removal (Oversized) The fascia can be removed via the self-tapping screws if required. Care should be taken not to lose the additional spacers. Right Front (Latch Side) ...
Comfort Comfort ARTUS™ ARTUS™ Troubleshooting General Alarms Fault Possible Cause Remedy/action Check ON/OFF switch is in the ON position. Unit will not start No power Check fuse (F1). Check power supply to the controller. No lights on controller when power is applied, check/replace Controller failure microprocessor.
Page 78
ARTUS™ ARTUS™ Comfort Comfort Troubleshooting Alarm Conditions Fault Possible Cause Status Remedy/action Control Panel LED Temperature discrepancy*. Non Critical General waterside/air side fault. Illuminated Condensate high level. Critical 2 Clear drain. Return air sensor alarm*. Critical 1 Check/replace sensor. Supply air sensor alarm*. Non Critical Check/replace sensor.
Page 79
All Airedale products or parts (non consumable) supplied for installation within the UK mainland and commissioned by an Airedale engineer, carry a full Parts & Labour warranty for a period of 12 months from the date of commissioning or 18 months from the date of despatch, whichever is the sooner.
Page 80