Optional Extras - AIREDALE EasiCool Technical Manual

Table of Contents

Advertisement

EasiCool™
Controls
Standard Network Features
As standard the AireTronix controller is capable of the providing a platform for the following and can be enabled on
request for 2 to 8 units, please specify at order:
Networking
A Local Area Network (LAN) can be used to connect up to 8 units to offer intercommunication and Duty/Standby control.
This also allows the connection of computers, printers and modems on the same communications ring.
For further details, please contact Airedale Controls.
When adding to an existing network, please consult Airedale to ensure strategy compatibility.
Duty/Standby Operation
The controller enables units to operate in run/standby mode, with up to 6 units networked together, without the need for
additional hardware or controllers. Standby units can be configured to start when the run unit has a critical alarm and/or
a high/low return air temperature alarm.
During peak demand, the standby units can temperature assist.
Duty Rotation
Networked units can be configured to duty rotate, providing equal hours run of fans and compressors.

OPTIONAL EXTRAS

Audible Alarm
The display keypad can be upgraded to include audible alerts.
BMS Interface Card
Enables Controlled units to be interfaced with most BMS, factory fitted, please contact Airedale.
A wide range of protocols can be accommodated through the use of interface devices. Available as a standard option
are: ModBus/Jbus, Carel and Trend.
For interfaces such as SNMP, LonWorks, Metasys and BACnet, please contact Airedale.
Also available is Airedale's own supervisory plug-in BMS card pCOWEB.
Based on Ethernet TCP/IP secure technology with SNMP features.
Requires no proprietary cabling or monitoring software and supplied pre programmed with an IP address for ease of set
up.
Water Detector
Two methods are available:
1
A solid state (probe) sensor is supplied loose for remote mounting on site.
2
Tape suitable for sensing water droplets is supplied loose for remote mounting on site. Standard tape
length 10m.
Water Detection Tape Installation
Monitored by a sensing relay, the water detection tape will provide an alarm when in contact with several drops of
conductive liquid. High humidity should normally not cause an alarm unless it results in condensation dripping on the
tape surface or condensation present on the surface to which the tape is applied.
Smoke Detector
Supplied loose for remote mounting to shut down the unit and activate the alarm upon sensing the presence of smoke.
Firestat
Installed in the return air stream to shut down the unit in the event of an unusually high return air temperature.
26
EasiCool Technical Manual 7525389 V1.8.0_05_2016
Precision Air Conditioning