ABB TPU2000 Technical Manual page 335

Modbus/modbus plus/ modbus tcp/ip automation
Table of Contents

Advertisement

7/3
51P-1 Timedial/delay (dial 1-10, delay 0-10, *20)
8/1
50P-1 Curve Select byte (Type II)
8/2
50P-1 Pickup X byte (0.5-20, *10)
8/3
50P-1 Timedial/delay high (dial *10,delay *100)
9/1
50P-1 Timedial/delay low (dial 1-10, delay 0-9.99)
9/2
150P-1 Curve Select byte (Type II)
9/3
150P-1 Pickup X byte (0.5-20, *10)
10/1
150P-1 Time Delay high byte (0-9.99, *100)
10/2
150P-1 Time Delay low byte
10/3
46-1 Curve Select byte (Type I)
11/1
46-1 Pickup Amp byte (1-12A *10, 0.2-2.4A *50)
11/2
46-1 Timedial/delay (dial 1-10, delay 0-10,*20)
11/3
51N-1 Curve Select byte (Type I)
12/1
51N-1 Pickup Amp byte (1-12A *10, 0.2-2.4A *50)
12/2
51N-1 Timedial/delay (dial 1-10, delay 0-10,*20)
12/3
50N-1 Curve Select byte (Type II)
13/1
50N-1 Pickup X byte (0.5-20, *10)
13/2
50N-1 Timedial/delay high (dial *10,delay *100)
13/3
50N-1 Timedial/delay low (dial 1-10, delay 0-9.99)
14/1
150N-1 Curve Select byte (Type II)
14/2
150N-1 Pickup X byte (0.5-20, *10)
14/3
150N-1 Time Delay high byte (0-9.99, *100)
15/1
150N-1 Time Delay low byte
15/2
87T-2 Tap Amp byte (2-9 Amp *10, 0.4-1.8 Amp *50)
15/3
51P-2 Curve Select byte (Type I)
16/1
51P-2 Pickup Amp/OA (1-12 Amp *10, 0.2-2.4Amp *50)
16/2
51P-2 Timedial/delay (dial 1-10, delay 0-10, *20)
16/3
50P-2 Curve Select byte (Type II)
17/1
50P-2 Pickup X byte (0.5-20, *10)
17/2
50P-2 Timedial/delay high (dial *10,delay *100)
17/3
50P-2 Timedial/delay low (dial 1-10, delay 0-9.99)
18/1
150P-2 Curve Select byte (Type II)
18/2
150P-2 Pickup X byte (0.5-20, *10)
18/3
150P-2 Time Delay high byte (0-9.99, *100)
19/1
150P-2 Time Delay low byte
19/2
46-2 Curve Select byte (Type I)
19/3
46-2 Pickup Amp byte (1-12A *10, 0.2-2.4A *50)
20/1
46-2 Timedial/delay byte (dial 1-10, delay 0-10, *20)
20/2
51G-2 Curve Select byte (Type I)
20/3
51G-2 Pickup Amp byte (1-12A *10, 0.2-2.4A *50)
21/1
51G-2 Timedial/delay byte (dial 1-10, delay 0-10, *20)
21/2
50G-2 Curve Select byte (Type II)
21/3
50G-2 Pickup X byte (0.5-20, *10)
22/1
50G-2 Timedial/delay high (dial *10,delay *100)
22/2
50G-2 Timedial/delay low (dial 1-10, delay 0-9.99)
22/3
150G-2 Curve Select byte (Type II)
23/1
150G-2 Pickup X byte (0.5-20, *10)
23/2
150G-2 Time Delay high byte (0-9.99, *100)
23/3
150G-2 Time Delay low byte
24/1
Disturb-2 Pickup X byte (0.5-5, *10)
24/2
Level Detector-1 PickupX (0.5-20, *10, 201=Disable)
24/3
Level Detector-2 PickupX (0.5-20, *10, 201=Disable)
25/1
spare
25/2
spare
25/3
spare
26/1
Unit Configuration byte
bit 0 : neutral tap range Wdg1 (0=1-12A, 1=0.2-2.4A)
bit 1 : phase tap range Wdg1 (0=1-12A, 1=0.2-2.4A)
bit 2 : neutral tap range Wdg2 (0=1-12A, 1=0.2-2.4A)
TPU2000/2000R Modbus/Modbus Plus Automation Guide
325