TPU2000/2000R Modbus/Modbus Plus/ Modbus TCP/IP Automation Guide
2/2
2/3
3/1
3/2
3/3
4/1
4/2
4/3
5/1
5/2
5/3
6/1
6/2
6/3
7/1
7/2
7/3
8/1
8/2
8/3
9/1
9/2
9/3
10/1
10/2
10/3
11/1
11/2-16/1
16/2
16/3
17/1
17/2
17/3
18/1
18/2
18/3
19/1
19/2
19/3
20/1
20/2
20/3
Wdg1 P CT Ratio low byte
Wdg1 N CT Ratio high byte (1-4000)
Wdg1 N CT Ratio low byte
Wdg2 P CT Ratio high byte (1-4000)
Wdg2 P CT Ratio low byte
Wdg2 G CT Ratio high byte (1-4000)
Wdg2 G CT Ratio low byte
Winding Phase Comp high byte (0-330, /30)
Winding Phase Comp low byte
Wind 1 CT Config high byte (0=Wye; 1=Delta, IA-IC; 2=Delta, IA-IB)
Wind 1 CT Config low byte
Wind 2 CT Config high byte (0=Wye; 1=Delta, IA-IC; 2=Delta, IA-IB)
Wind 2 CT Config low byte
Phase Rotation high byte (0=ABC, 1=ACB)
Phase Rotation low byte
Alt 1 Settings high byte (0=Disable, 1=Enable)
Alt 1 Settings low byte
Alt 2 Settings high byte (0=Disable, 1=Enable)
Alt 2 Settings low byte
Trip Failure Mode high byte (Type Trip Failure)
Trip Failure Mode low byte
Trip Failure Time high byte (5-60)
Trip Failure Time low byte
Trip Fail Dropout % PU high byte (5-90)
Trip Fail Dropout % PU low byte
Configuration Flag high byte
bit 8 : Cross Block Mode (0=Disable, 1=Enable)
bit 9 : SPARE
bit 10 : SPARE
bit 11 : SPARE
bit 12 : SPARE
bit 13 : SPARE
bit 14 : SPARE
bit 15 : SPARE
Configuration Flag low byte
bit 0 : OC Protect Mode (0=Fund, 1=RMS)
bit 1 : Reset Mode (0=Instant 1=Delayed)
bit 2 : Spare
bit 3 : Target Display Mode (0=Last, 1=All)
bit 4 : Local Edit (0=Disable, 1=Enable)
bit 5 : Remote Edit (0=Disable, 1=Enable)
bit 6 : WHr/VARHr Meter Mode (0=KWHr, 1=MWHr)
bit 7 : LCD Light (0=Timer, 1=On)
Unit Name character 1-15
Transformer Configuration Byte (0=Wye1-Wye2, 1=Wye1-Delta2, 2=Delta1-Wye2, 3=Delta1-
Delta2)
Demand Time Const high byte (Type Demand Time)
Demand Time Const low byte
LCD Contrast Adj high byte (0-63)
LCD Contrast Adj low byte
Relay Password character 1
Relay Password character 2
Relay Password character 3
Relay Password character 4
Meter Winding Mode (0=Wdg1, 1=Wdg2, 2=Wdg3)
VT Configuration (0=69VWye, 1=120VWye, 2=120V Delta, 3=208V Delta)
VT Ratio high byte (1-4500)
VT Ratio low byte
Spare
288