Figure 5-71. Global Register Configuration Option Screen

The screen shown in Figure 5-72 is visible once the Set Global Register Screen is depressed. Double clicking the
area over the register assignment field then allows the sub "window" to be visible. In this example, Ia (Phase A
Current Register 257) is mapped to Global Register 1. The register address is found by referencing Table 5-81 of
this document.

Table 5-81. Modbus Plus Global Register Map Configuration Definition

Register
Item
Address
62560
SPARE_1
62561
Execute Register
0 = No Action
1 = Update Registers
2 = Refresh Registers
62562
Access Password
TPU2000/2000R Modbus/Modbus Plus Automation Guide

Figure 5-72. Global Register Configuration Screen

Description
Unsigned 16 Bits
ASCII – 2 Characters Leftmost Digits