Figure 5-45. Typical Modbus/Modbus Plus Register Definition

During the commissioning process, it is required that the correct data is mapped from the relay to the host device.
The conventional method is to have an individual with expensive test gear to apply individual voltages and
currents to the relay terminals to simulate field conditions. The individual must be at the substation and a direct
link must be made to the individual at the host device verifying the correct data is being received and interpreted
correctly.
With 6X memory and some of the 4X memory, a host device can force the read/write capable 4X and 6X memory
locations and verify data is sent and received to some memory location. The SCADA REDI® provides much
more flexibility allowing streamlining of the commissioning process.
Within the TPU2000 and TPU2000R control register memory map a single bit (Bit 13 in Register 41415) may be
set to allow READ, WRITE, and READ/WRITE Modbus/Modbus Plus commands to be sent to the previously
READ ONLY memory locations. A typical scenario is illustrated in Figures 5-44 and 5-45.
TPU 2000
C
C
E
E
TARGETS
OR
C
E
TPU 2000R
SCADA REDI(R) BIT = 0
OX
Memory
(READ Only)
TPU 2000
1X
C
C
E
E
Memory
(READ Only)
TARGETS
4x
Memory
(READ ONLY)
OR
(READ/WRITE)
CAPABLE
QUASI-
READ/WRITE
C
E
CAPABLE
File 10
File 2
TPU 2000R
File 1
6X
Memory
READ/WRITE
Capable
Figure 5-46. SCADA REDI® Memory Map Modification
00001
OX
Memory
(READ Only)
01056
10001
1X
Memory
(READ Only)
11056
40001
4x
Memory
41182
(READ ONLY)
41409
(READ/WRITE)
CAPABLE
41457
( QUASI-
41665
READ/WRITE
CAPABLE)
42945
File 10
60000
File 2
File 1
6X
Memory
READ/WRITE
Capable
63199
SCADA REDI(R) BIT = 1
00001
OX
Memory
(READ Only)
01056
10001
1X
Memory
(READ Only)
11056
40001
41182
41409
4X
(READ/WRITE)
41457
CAPABLE
41665
42925
File 10
60000
File 2
File 1
6X
Memory
READ/WRITE
Capable
63199
HOST
00001
01056
10001
11056
40001
42925
60000
63199
138

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Tpu2000r

Table of Contents