Table 5-28. Physical Output Table (1 Register Defined) - ABB TPU2000 Technical Manual

Modbus/modbus plus/ modbus tcp/ip automation
Table of Contents

Advertisement

Bit 4 = Reserved
Bit 3 = Reserved
Bit 2 = Reserved
Bit 1 = Reserved
Bit 0 = Reserved
41164
Logical Input
Reserved
41165
Logical Input
Bit 15 = 51P-3 (Note 3)
Bit 14 = 51N-3 (Note 3)
Bit 13 = 50P-3 (Note 3)
Bit 12 = 50N-3 (Note 3)
Bit 11 = 150P-3 (Note 3)
Bit 10 = 150N-3 (Note3)
Bit 9 = 46-3 (Note 3)
Bit 8 = 51G
Bit 7 = 50G
Bit 6 = 150G (Note 3)
Bit 5 = ECI3 (Note 3)
Bit 4 = Reserved
Bit 3 = Reserved
Bit 2 = Reserved
Bit 1 = Reserved
Bit 0 = Reserved
41166
Logical Input
Reserved
41167
Logical Input
Reserved
41168
Logical Input
Reserved
NOTE 1: Drop Out Time is 3 cycles for Alarm Signals. The alarms activate with each operation or power-up
until the counters are reset. The counter alarms are reset when the targets are reset.
NOTE 2: Two Winding Relay Only
NOTE 3: Three Winding Relay Only
(L): This signal is latched and is only reset upon a protocol control command (Section 3), WinECP, ECP, or
Front Panel Interface reset sequence.

Table 5-28. Physical Output Table (1 Register Defined)

Register
Item
41169
Bit 15 = Reserved
Bit 14 = Reserved
Bit 13 = Reserved
Bit 12 = Reserved
Bit 11 = Reserved
Bit 10 = Reserved
Bit 9 = Reserved
Bit 8 = Reserved
Bit 7 = OUT 7
Bit 6 = OUT 6
Bit 5 = OUT 5
Bit 4 = OUT 4
Bit 3 = OUT 3
Bit 2 = OUT 2
Bit 1 = OUT 1
Bit 0 = TRIP
TPU2000/2000R Modbus/Modbus Plus Automation Guide
Reserved
Reserved
Reserved
Reserved
Reserved (lsb rightmost)
Unsigned Integer 16 Bits
Reserved
Unsigned Integer 16 Bits
Winding 3 Phase Instantaneous Overcurrent Control Enabled
(msb leftmost)
Winding 3 Neutral Instantaneous Overcurrent Control Enabled
st
1
Winding 3 Phase Time Overcurrent Control Enabled
st
1
Winding 2 Neutral Time Overcurrent Control Enabled
nd
2
Winding 3 Phase Time Overcurrent Control Enabled
nd
2
Winding 2 Neutral Time Overcurrent Control Enabled
Winding 3 Negative Sequence Control Enabled
Ground Time Overcurrent Function Enabled
st
1
Ground Instantaneous Overcurrent Function Enabled
nd
2
Ground Instantaneous Overcurrent Function Enabled
Storage of Data Fault Summary Capture Initiated
Reserved
Reserved
Reserved
Reserved
Reserved (lsb rightmost)
Unsigned Integer 16 Bits
Reserved
Unsigned Integer 16 Bits
Reserved
Unsigned Integer 16 Bits
Reserved
Description
16 Bit Unsigned Integer
(msb leftmost bit)
(lsb rightmost bit)
109