One should note the operation record event codes are arranged in groups to easily indicate the type of error
dependent on the value of the operation record. Table 5-39 lists the Operation Record Event Codes.

Table 5-39. Operation Record Address Definition

Register
Address
42049
EvtRecCtlReg
1 = First Record
2 = Next Record
3 = Last Unreported Record
42050
Year (0-99)
42051
Month
42052
Day
42053
Hour
42054
Minute
42055
Second
42056
Hundredths of a Second
42057
Message Number
42058
VALUE ?
42059
Operation Number

Table 5-40. Event Record Definition Type

Event Record Type (Register 42058 code definition)
Operation Number
00
01
02
03
04
05
06
07
08
09
10
11
12
13
14
15
16
17
18
19
31
32
33
34
35
40
41
42
TPU2000/2000R Modbus/Modbus Plus Automation Guide
Item
Fault Record Control Register
Unsigned 16 Bit
1 = Fill 42050 – 42059 with First Record Data.
2 = Fill 42050 – 42059 with next Record Data pointed to in
buffer.
3 = Fill 42050 – 42059 with the last unreported record of
data between the last data access
Unsigned 16 Bit Year of Event
Unsigned 16 Bit Month of Event
Unsigned 16 Bit Day of Event
Unsigned 16 Bit Hour of Event
Unsigned 16 Bit Minute of Event
Unsigned 16 Bit Second of Event
Unsigned 16 Bit Hundredth Second of Event Date
Unsigned Integer 16 Bits 0<=Range <=999
Who the hell knows?
16 Bit Unsigned
See Table XX
Definitions
87TTrip
87H Trip
51P-1 Trip
51N-1 Trip
50P-1 Trip
50N-1 Trip
150P-1 Trip
150N-1 Trip
46-1 Trip
51P-2 Trip
51G-2 Trip
50P-2 Alarm
50G-2 Alarm
150P-2 Block
150G-2 Trip
46-2 Restore
ECI-1
ECI-2
Through Fault
Harmonic Rest
Fault Clear Failed
Fault Cleared
Harmonic Restraint
Manual Trip
Manual Trip Failed
87T Enabled
87H Enabled
51P-1 Enabled
Description
131