TPU2000/2000R Modbus/Modbus Plus/ Modbus TCP/IP Automation Guide
169
170
171
172
173
174
175
176
177
178
179
180
181
Msg byte
1/1
1/2
1/3
2/1
2/2
2/3
3/1
3/2
3/3
4/1
4/2
4/3
5/1
5/2
5/3
If the operation entry doesn't exist then send 0's in all the bytes 2/1 through 5/3.
5.13 Send Next Operations Record ( 3 5 13 )
Same format as ( 3 5 12 ) except Msg 1/2 = 0x5d.
5.14 Breaker Status (Including I/O Status) ( 3 5 14 )
Input status bit 0=opened, 1=closed.
Output status bit 0=de-energized, 1=energized.
Msg byte
1/1
1/2
1/3
2/1
2/2
ULI4 Input Opened
ULI5 Input Closed
ULI5 Input Opened
ULI6 Input Closed
ULI6 Input Opened
ULI7 Input Closed
ULI7 Input Opened
ULI8 Input Closed
ULI8 Input Opened
ULI9 Input Closed
ULI9 Input Opened
CRI Input Closed
CRI Input Opened
Definition
Relay Status (see command 3 4 1, msg 1/1)
Command + Subcommand = 0x5c
Total Number of Messages = 5
Year
Month
Day
Hour
Minute
Second
Hundredths of second
Message Number
Value (if any) Hi byte
Value (if any) Lo byte
Operation Number (high byte)
Operation Number (low byte)
Definition
Relay Status (see command 3 4 1, msg 1/1)
Command + Subcommand = 0x5e
Total Number of Messages = 3
Contact Input Status (high byte)
Bit 0 - Input 9
Bit 1 - Spare
Bit 2 - Spare
Bit 3 - Spare
Bit 4 - Spare
Bit 5 - Spare
Bit 6 - Spare
Bit 7 - Spare
Contact Input Status (low byte)
Bit 0 - Input 1
Bit 1 - Input 2
Bit 2 - Input 3