3. Insert each 8-32 x 5/16 in. screw through the holes in the bracket and into the
4. Repeat step 1 through step 3 to attach the left front bracket 2 to the left side
Figure 4. Position the front bracket

Installing the switch in the cabinet

Complete the following steps to install the switch in the cabinet.
1. Position the switch in the cabinet, as shown in Figure 5 on page 12, providing
2. Attach the right front bracket 1 to the right front rack rail using two 10-32 x
3. Repeat step 2 to attach the left front bracket 2 to the left front rack rail and
install the switch in a recessed position in the cabinet, use the bracket holes
that are set back from the end of the bracket.
corresponding hole in the switch and tighten all 8-32 x 5/16 in. screws to a
torque of 15 in-lb (17 cm-kg).
of the switch.
2
1
temporary support under the switch until the rail kit is secured to the cabinet.
5/8 in. screws 3 and two retainer nuts 4 .
tighten all 10-32 x 5/8 in. screws to a torque of 25 in-lb (29 cm-kg).
3
Chapter 2. Installing and configuring the switch
11