Q7 Flow Control Panel Features - Toshiba Q7 Flow Installation And Operation Manual

Q7 flow adjustable speed drive
Table of Contents

Advertisement

Q7 Flow Control Panel Features

There are three types of Q7 Flow control panels available. The panel used will be a function of the
system features available for a given system. Two of the panels provide the user with control and
monitoring features and one is used as a cover for an unused panel mounting hole and has no active
features.
Figure 11
each.
Figure 11. Available Q7 Panels.
Panel Items
1.
Control Power LED (LED 5) — On when the control circuit power is available. This is not an
indication that power is off.
2.
System Interlock LED (LED 4) — On when the following conditions are met:
3.
Inverter LED (LED 2) — On when the following conditions are met:
This closes the 1M and 2M contactors allowing for normal ASD operation.
30
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
shows the three Q7 Flow panel types followed by a description of the applicable features of
Control Power is applied,
Door switch (LS) is closed,
Protective Overload contactor (OL) is closed,
Customer Interface contact (CI) is closed, and
The damper is fully open (DRA connected to DRB).
Control Power is applied,
Door switch (LS) is closed,
Protective Overload contactor (OL) is closed,
Customer Interface contact (CI) is closed, and
The Inverter Mode switch is switched to INV.
Q7 Flow Installation and Operation Manual

Advertisement

Table of Contents
loading

Table of Contents