I/O and Control

The ASD can be controlled by several input types and combinations thereof, as well as operate within a
wide range of voltage levels. This section discusses the ASD control methods and supported I/O
functions.
The Control Terminal Strip PCB (P/N 53750; shown on
analog I/O functions.
descriptions of the input and output terminals of the Control Terminal Strip PCB.
Terminal
Input/Output
Name
ST
Discrete Input Standby — Multifunctional programmable discrete input (connect to CC to operate the unit).
RES
Discrete Input Reset — Multifunctional programmable discrete input.
F
Discrete Input Forward — Multifunctional programmable discrete input.
R
Discrete Input Reverse — Multifunctional programmable discrete input.
S1
Discrete Input
S2
Discrete Input Preset Speed 2 — Multifunctional programmable discrete input.
S3
Discrete Input Damper Fdbk — Multifunctional programmable discrete input (connect to CC to operate the unit).
S4
Discrete Input Emergency Off — Multifunctional programmable discrete input (connect to CC to operate the unit).
CIA/CIB
Discrete Input
DRA/DRB Discrete Input
RR
Analog Input
RX
Analog Input
II
Analog Input
VI
Analog Input
P24
DC Output
PP
DC Output
DSA/DSB
Discrete Output
(OUT1)
Discrete Output Acc/Dec Complete — Multifunctional programmable output that changes state when the programmed
OUT2 A/B
Discrete Output
FLA
Discrete Output Fault Relay - rated at 2A/250 VAC (N.O.). Connects to FLC at power up.
FLB
Discrete Output Fault Relay - rated at 1A/250 VAC (N.C.). Disconnects from FLC at power up.
FLC
Discrete Output Fault Relay - rated at 2A/250 VAC (com). Connects to FLA at power up. Connects to FLB at Fault.
FP
Output
AM
Output
FM
Output
CC
Discrete Input Terminals
Analog Input Terminals reference CC.
Note:
Multifunctional terminals are shown in the default setting condition.
Q7 Flow Installation and Operation Manual
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
Table 1
lists the names, the default settings (where applicable), and the
Table 1. Input/Output terminal names and functions.
Function (Default for programmable terminals)
Fire Speed
— Multifunctional programmable discrete input.
Customer Interlock — The CIA-to-CIB connection is accomplished via a jumper, a relay, or some other
user-selected means and is required for normal system operation.
Damper Response — The DRA-to-DRB connection is accomplished via limit switches at the fully-
opened damper and is required for normal system operation.
RR — Multifunction programmable analog input (0.0 to 10 volt input — 0 to 80 Hz output).
RX — Multifunctional programmable analog input (-10 to +10 VDC input — Unassigned).
II — Multifunctional programmable analog input (4 to 20 mADC input — Unassigned).
VI — Multifunctional programmable analog input (0 to 10 VDC input — Unassigned).
24 VDC @ 50 mA output.
PP — 10.0 VDC voltage source for the external potentiometer.
Damper Command — Multifunctional programmable output that is used to open/close the 120 VAC
damper motor power circuit when the motor is ASD-driven (see
acceleration or deceleration ramp is reached.
Frequency Pulse — Multifunctional programmable output that produces a pulse train that has a
frequency which is based on the output frequency of the ASD.
Output Current — Multifunctional programmable output that produces a DC current that is proportional
to the magnitude of the output current.
Output Frequency — Multifunctional programmable output that produces a DC current that is
proportional to the magnitude of the output frequency.
Control common (Do Not connect to Earth Gnd).
On = connected to CC.
pg.
18) of the Q7 Flow supports discrete and
Q7 Flow Theory of Operation on pg.
32).
15