D. Control Power/Potential Transformers
A control power transformer (Fig. 27) is fix-mounted on the floor of
the controller compartment. Power is supplied to the fused primary
of the control power transformer from the load side of the main
power fuses.
Optionally, a second transformer (Fig. 28), normally used as an
instrument transformer, can be mounted in the compartment.
When this option is supplied, the two transformers are normally
connected in an open-delta arrangement.
Another option sometimes supplied is a second control power
transformer connected in parallel with the first to increase the
available KVA capacity.
Both the control and optional potential transformer are used to
supply power to the low voltage circuits of the controller. This
includes power for the vacuum contactor operating coil and
instrumentation. Reference the equipment's schematic drawing(s)
for details.
An electrical interlock is provided to ensure that all load is
disconnected from the control power transformer secondary
winding before the power isolation switch can be opened or closed.
TOSHIBA
JK Series 720 Controllers
Fig. 27 Control Power Transformer
Fig. 28 Optional 2
nd
Transformer
17