4.
Bypass LED (LED 3) — On when the following conditions are met:
This opens the 2M contactor and closes the 3M contactor.
5.
Inverter Mode Switch — With the System Interlock LED criteria being met, the Inverter Mode
switch allows the user to switch the system to the Inverter Mode, the Bypass Mode, or Off.
6.
Inverter Test Mode Switch — With the CPT input power applied and the door closed, the
Inverter Test Mode switch closes the 1M contactor (via K1) to test the ASD section of the system
without providing an output to the connected motor.
7.
Test LED (LED 1) — On during Test Mode operation.
Q7 Flow Installation and Operation Manual
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
Control Power is applied,
Door switch (LS) is closed,
Protective Overload contactor (OL) is closed,
Customer Interface contact (CI) is closed,
The damper is fully open (DRA connected to DRB), and
The Inverter Mode switch is switched to BYP.