Alert Messages In Ams Wireless Configurator And Field Communicator - Emerson Rosemount 3308A Reference Manual

Wireless guided wave radar, rosemount 3308 series
Hide thumbs Also See for Rosemount 3308A:
Table of Contents

Advertisement

Reference Manual
00809-0100-4308, Rev BB
6.2.2
Alert messages in AMS Wireless Configurator and Field
Communicator
Table 6-1
Configurator and Field Communicator.
To view Active Alerts, do the following:
From the Home Screen, go to Service Tools > Active Alerts.
Table 6-1. Failure Alerts (F:)
Message
Electronics Failure
Radio Failure
Supply Voltage Failure
Probe Disconnected
Electronics Temperature
Critical
Remote Housing Error
Configuration Error
Service and Troubleshooting
to
Table 6-4
shows list of alert messages that may be displayed in the AMS Wireless
Description
An electronics error that could impact the
device measurement reading has occurred.
The wireless radio has detected a failure or
stopped communicating.
The supply voltage is too low and will affect
device operation.
The device cannot detect the probe.
The internal temperature of the device has
reached critical levels and the integrity of the
device electronics may be compromised.
Environmental temperature should not
exceed device specifications.
The device has detected a problem associated
with the remote housing.
The device has detected a configuration error.
Reasons may be multiple.
See
Table 6-2
for a list of detailed
Configuration Errors that may be displayed.
Service and Troubleshooting
Recommended actions
1. Restart the device.
2. Restore default settings and reconfigure the device.
3. If the condition persists, replace the device.
1. Restart the device.
2. If the condition persists, replace the device.
1. Replace the Power Module, see
replacement" on page
101.
1. Check that the probe connection is properly
tightened.
2. Check that the probe connection is dry and clean.
3. Restart level measurements.
4. If the condition persists, replace the device and/or
the probe.
1. Verify that ambient temperature is within the
specified range. For more information about the
maximum ambient temperature, see
limits" on page
108.
2. Remote mount the transmitter head away from the
process and environmental conditions.
3. Restart the device.
4. If the condition persists, replace the device.
1. Correct remote housing configuration to match
connected remote housing cable.
2. Check remote housing cable.
1. Click on the Details button for more information.
2. Correct the parameter causing the configuration
error.
October 2016
"Power module
"Temperature
81