Section 6: Service and Troubleshooting
December 2014
6.2.2
Alert messages in AMS Wireless Configurator and Field
Communicator
Table 6-1
Configurator and Field Communicator.
To view Active Alerts, do the following:
Table 6-1. Failure Alerts (F:)
Message
Electronics Failure
Radio Failure
Supply Voltage Failure
Probe Disconnected
Electronics Temperature
Critical
Remote Housing Error
Configuration Error
74
to
Table 6-4
shows list of alert messages that may be displayed in the AMS Wireless
From the Home Screen, go to Service Tools > Active Alerts.
Description
An electronics error that could impact
the device measurement reading has
occurred.
The wireless radio has detected a failure
or stopped communicating.
The supply voltage is too low and will
affect device operation.
The device cannot detect the probe.
The internal temperature of the device
has reached critical levels and the
integrity of the device electronics may
be compromised. Environmental
temperature should not exceed device
specifications.
The device has detected a problem
associated with the remote housing.
The device has detected a configuration
error. Reasons may be multiple.
See
Table 6-2
for a list of detailed
Configuration Errors that may be
displayed.
Reference Manual
00809-0100-4308, Rev BA
Recommended actions
1. Restart the device.
2. Restore default settings and reconfigure the
device.
3. If the condition persists, replace the device.
1. Restart the device.
2. If the condition persists, replace the device.
1. Replace the Power Module, see
module replacement" on page
1. Check that the probe connection is properly
tightened.
2. Check that the probe connection is dry and
clean.
3. Restart level measurements.
4. If the condition persists, replace the device
and/or the probe.
1. Verify that ambient temperature is within
the specified range. For more information
about the maximum ambient temperature,
see
"Temperature limits" on page
2. Remote mount the transmitter head away
from the process and environmental
conditions.
3. Restart the device.
4. If the condition persists, replace the device.
1. Correct remote housing configuration to
match connected remote housing cable.
2. Check remote housing cable.
1. Click on the Details button for more
information.
2. Correct the parameter causing the
configuration error.
Service and Troubleshooting
"Power
97.
103.