CAIRplus
8.4.3 Commissioning of direct-driven fan assembly
DANGER!
8.4.4 Maintenance of direct-driven fan assembly
DANGER!
PR-2009-0096-GB • Subject to modifications • R8-10/2015
Please consider the safety instructions on page 5 and page 56 when performing
all the described activities!
Remove remaining installation debris and foreign matter from the impeller and air
intake zone.
Check motor protection for correct setup (also see separate project-related
documentation and/or „Motor protection" on page 50).
Δ
With Y/
starting, set up the motor protection device for 58% of the rated current if
the phase current flows through the latter – i.e. motor protection device must be
installed between motor terminals U1, V1, W1 and not in mains supply line upstream
of the control unit.
It is not allowed to activate the parameter "overmodulation" as this can damage the
impeller.
Notice!
In this case, DencoHappel neither accepts warranty claims nor assumes liability.
Besides, ensure that the maximum frequency does not exceed the allowable limit
(refer to data sheet on fan).
Consider the relevant instructions specified in the enclosed manual for the
frequency inverter. Use a screened motor cable only.
Please consider the safety instructions on page 5 and page 55ff when performing
all the described activities!
Carry out the following maintenance steps:
Check electric motors for dirt, damage, corrosion and secure mounting.
Check electric motors for noise in bearings, if required, engage qualified licensed
staff to replace bearings.
Check impeller, especially welded seams for possible cracks; if required, engage
qualified licensed staff to replace bearings.
Commissioning and Maintenance
67