Routine Cleaning And Maintenance - Denco CAIRplus Operation Manual

Modular air handling units
Table of Contents

Advertisement

Commissioning and Maintenance
Maintenance intervals
8.1

Routine cleaning and maintenance

Observe current legal regula-
tions and standards! We rec-
ommend to perform
maintenance steps and ob-
serve intervals specified in
VDI 6022
56
Risk of damage to the unit!
When entering CAIR units, ensure that no loads are applied on the floor
panels.
For all installation work, take appropriate measures to ensure that the load
is evenly distributed across the bottom profiles.
The specified maintenance intervals apply to air conditions with normal levels of con-
tamination. The maintenance intervals must be reduced according to the level of air
contamination.
Notice!
Carry out additional cleaning if treated air contains oil. Sealant material is oil-proof
only for a limited time. When using disinfectants, only use those according to
DGHM list, DVG or VAH certification.
PERSONAL PROTECTION!
For cleaning and certain maintenance jobs, use personal protective
equipment including face shield and chemical resistant gloves.
HAZARDOUS VOLTAGE AND RISK OF ROTATING COMPONENTS!
OBSERVE PERSONAL PROTECTION MEASURES
Please consider the safety instructions on page 55.
After the cleaning procedure ensure that the unit is dry and residue-free!
Use a dry cloth or an industrial vacuum cleaner, if necessary, to remove dry coarse
dirt.
Remove remaining dirt following a subsequent installation of add-on accessory
items.
For other contaminants use a dry cloth to remove dirt, if applicable wash off using
some water by adding alkaline cleaning agent.
For disinfectioning unit surfaces use cleaning agents specified in the following
sources: "List of disinfection procedures (DGHM)" issued by the German
Association for Hygiene and Microbiology, certificates issued by DVG and VAH
(German Association of Veterinary Medicine and the German Association for
Hygiene and Microbiology/Association for Applied Hygiene). Refer to this list for
details and consider the specified concentration and exposure time. Use the
following cleaning agents: e.g. BODE Microbak or DESOMED Desotop. For correct
concentration refer to the data sheet provided by the manufacturer and/or select a
non-visible small surface to test the solution there beforehand.
Using alcohol-containig agents is not allowed due to risk of explosion and fire.
Do not use abrasive sponges or tools that may scratch or scrape the protective
surface during cleaning (surface can be damaged).
Treat galvanized parts with a preservative spray.
Apply a lubricant spray to all moving parts, such as door latches and hinges, with the
exception of dampers and louvres!
Clean gaskets on the inspection doors and check for leaks, microbial growth and
mould. It is recommended to treat gaskets with a waterproof preservative.
Check electrical connections.
Check earthing.
Ensure that the unit is dry and residue-free!
ATTENTION
PR-2009-0096-GB • Subject to modifications • R8-10/2015
CAIRplus