Denco CAIRplus Operation Manual page 60

Modular air handling units
Table of Contents

Advertisement

Commissioning and Maintenance
Unit part
Frequen-
cy
(months)
Every 12
Cooler with-
months
out or with
droplet sepa-
rator
(see page 73)
Before
winterizati
on
Every 12
Evaporator/
months
condenser
(see page 75)
Every 12
Heat pipe
months
(see page 76)
Every 12
Liquid-cou-
months
pled energy
recovery as-
sembly
(see page 76)
Every 12
Plate heat
months
exchanger
(see page 77)
Rotation heat
Every 3
exchanger
months
(refer to
Every 12
page 78)
months
60
Action
Check for leak-free condition and possible dirt on the air side.
To ensure frost protection, periodically check the safety devices and take proper
precautions such as draining the equipment or adding antifreeze agents.
Ensure that pipework connections and mountings are securely fixed.
Clean on air side, if necessary (blow through heat exchanger using compressed
air or low pressure water).
Air vent.
Clean coil drip tray and condensate line.
Check trap for proper operation, top up as necessary.
Clean droplet separator with a descaling spray.
Drain water from the cooling coil before winter.
Clean and check evaporator/condenser.
Ensure that all refrigeration components (refrigerating machine, direct
evaporator, distribution manifold, refrigerant lines, etc.) are functioning properly.
Clean coil fins.
Clean coil drip tray and condensate line.
Check trap for proper operation, top up as necessary.
If a heat pipe is fitted with a bypass, check air-regulating and shut-off dampers
for proper operation.
Complete the same steps specified in "Cooler with/without droplet separator"
(every 12 months).
Carry out cleaning depending on contamination degree of the plate assembly.
Check bypass damper for proper operation, if required.
Complete wet cleaning only if a tray is installed and available!
Remove oil and fat deposits.
Check tension of drive belt, tighten as necessary.
Clean coil fins – carry out wet cleaning only if a tray is installed! Never use high-
pressure water or steam for cleaning coil fins.
Remove dirt from the section.
Check dampers with energy-recovery system and bypass arrangement for
proper operation.
Check run-around gaskets, adjust as necessary.
Check motor alignment.
PR-2009-0096-GB • Subject to modifications • R8-10/2015
CAIRplus