Denco CAIRplus Operation Manual page 28

Modular air handling units
Table of Contents

Advertisement

Assembly
Required tools:
5.2.1 Removing lifting lugs and safety devices
Roof lifting
lug
Cylinder
screw
Plastic
washer
Support
bushing
Fig. 5-9:
Lifting lug at joints
Lifting lug
at roof
Cylinder
screw
Plastic
washer
Support
bushing
Fig. 5-10:
Lifting lugs for roof and end wall
28
– Electric screwdriver, drill
– Bit holders/sockets
– Sockets of sizes 8, 10
– Slotted head screw bits, sizes 2, 3
– Open-ended spanners sizes 8, 13, 17
– Screw drivers 4.5 - 6.5
– Hexagon socket size 6
– Tensioning belts or suitable hoisting device
Remove all lifting lugs, safety locks and devices mounted on and in the unit prior to
assembly.
Remove safety locks on the fan.
Verify that that all lifting lugs on the roof are removed:
Notice!
Due to a risk of damage through lifting lugs - externally mounted dampers, flexible
canvas connection partially ship separately.
Mount these components on-site and seal them.
Remove the lug, screw and bushing at the section joint, then
secure the supplied M8 x 30 screw.
Remove the screws on the end walls and secure the sup-
plied M8 x 70 screw.