3.3.1 Ambient conditions
Outdoor air
Extract air
Air humidity
Max. operating pressure
and temperature
Minimum operating tempera-
Notice on extreme
conditions!
3.3.2 Permitted storage conditions / permitted air condition for uninstalled units
Air temperature
Air humidity
3.3.3 Supply voltage
3.3.4 Condensation limits
16
Note on extreme conditions!
In addition to the air temperature/air humidity of the transported medium, the tem-
perature/humidity of the ambient air is also critical. Observe the condensation lim-
its.
from -25 °C to +60 °C
from 0 °C to +80 °C
depending on temperature max. 18 g/kg of dry air
Heating/cooling coil 16 bar / 90 °C
Heating/cooling coil 6 °C
ture
In addition to the air temperature/air humidity of the transported medium, the temper-
ature/humidity of the ambient air is also critical. Environmental factors such as proxim-
ity to sea or ocean must be taken into account when selecting material quality.
Different ambient conditions apply for integrated refrigerating unit.
-10 °C to +50 °C
Store units in a dry, non-condensing atmosphere
The required supply voltage is specified in the order-related documentation, e.g. AC
230 V/50 Hz (1 phase) or AC 400 V/50 Hz (3 phases).
Please pay due attention to condensation limits!
The following diagrams illustrate condensation limits depending on temperature and
relative humidity at the installation site - for series CAIRplus SX M and CAIRplus SX K.
The diagrams are based on normal air values and are calculated using a model box.
The given values are approximate figures and can not be used as a guarantee for
avoiding condensation. Depending on different casing components, deviations are
possible.
PR-2009-0096-GB • Subject to modifications • R8-10/2015