CAIRplus
5.1.3 Foundation requirements for indoor installation
L ≤ 1600
Fig. 5-4:
Foundation requirements with side-by-side units
operator side
Fig. 5-5:
Foundation requirements with side-by-side
cross-section
PR-2009-0096-GB • Subject to modifications • R8-10/2015
L ≤ 1600
The foundation/bottom base may protrude a maximum of 20
mm beyond the outer edge of the unit to enable mounting of
cover plates or accessories, such as condensate traps.
The supporting points of the foundation must be located at
every shipping split. Besides, ensure that the maximum dis-
tance between these points does not exceed 1600 mm in the
unit length(see fig. 5-4).
Units with side-by-side arrangement must be supported in
the center (see fig. 5-5).
Assembly
25