A5.0 DRAWOUT OPERATION

A5.1 INSERTING THE RELAY

Before the MD-3001 is inserted into the Drawout
Enclosure:
Verify that all wiring is correct as shown in the wiring
diagram.
When inserting the MD-3001 Drawout into the Drawout
Enclosure, use the guides to align the exterior of the
device chassis with the interior of the enclosure. Slide the
unit into the Case using the guides, pressing firmly until all
four latches located on the sides of the device are seated
and latched into place. Tabs on the MD-3001 Drawout
Inner Chassis will prevent the inner chassis from being
inserted upside down or being inserted into an enclosure
of another IQ product.
Fig. A-4 MD 3001 Typical Wiring Diagram
For more information visit:
www.EatonElectrical.com
Initial Release
THE MD-3001 INNER CHASSIS MUST BE FULLY
INSERTED AND FULLY LATCHED IN TO ITS
DRAWOUT ENCLOSURE FOR PROPER
OPERATION OF THE DEVICE.
When the unit is seated properly, the quick release buttons
at the top and bottom of the unit will return to their non-
compressed position. The device can now be secured in
the enclosure by inserting a utility locking ring in the
provided slot.

A5.2 REMOVING THE RELAY

WARNING
REMOVAL OF THE MD-3001 INNER CHASSIS
FROM THE DRAWOUT OUTER CASE EXPOSES
LIVE PARTS, WHERE THE HAZARD OF A FATAL

Advertisement