Symptom
Operational LED is
Off
Operational LED is
On but Does not Blink
Operational LED
Blinks Red
Operational LED is
NOT Definite Red or
Green
"PGRM" Appears in
Settings Display
Window
"ERR" Appears in
Setting
"RAM" Appears in
Settings Display
Window
Current Readings
Appear Incorrect
Protective Relay
Indicates a Trip, but
Circuit Breaker
Doesn't Open
Manual Reset
Function not
Operational
Caution: When the MD-3000 Protective Relay is Powered, it Supplies Voltage to the "b" Contacts
TABLE 5.1 TROUBLESHOOTING GUIDE
Probable Cause
Protective Relay's Control
Power is Deficient or
Absent
Protective Relay is
Malfunctioning
Protective Relay's Control
Power is Deficient or
Absent
Protective Relay is
Malfunctioning
Internal Problem Detected
Internal Problem Detected
Set points are Invalid
Check sum did not Match
There was an Error While
in the Test Mode
An Internal RAM Check
Failed
Incorrect CT Ratio used in
Equipment
Incorrect Current Wiring
Incorrect System
Frequency Programmed
Improper Wiring from
Protective Relay
Unit in Test Mode with "No
Trip Test Selected"
Damaged Reset
Pushbutton
For more information visit:
Possible Solution(s)
Verify that Control Power is Connected
Between TB1 -5 and B1 -6 and that it is
within Specifications
Replace the Protective Relay
Verify that Control Power is Connected
Between TBI-5 and TBI-6 and it is within
Specifications
Replace the Protective Relay
Press Reset Pushbutton
Reprogram Set points
Replace Protective Relay if Symptom
Persists
Press Reset Pushbutton
Reprogram Set points
Replace Protective Relay if Symptom
Persists
Reprogram Set points
Replace Protective Relay if "PGRM"
Reappears After Saving Settings
More than 0.1 Per Unit of Current Cannot
Flow While in Test Mode
Remove Power from the Protective
Relay and then Reapply Power - If the
Symptom Persists, Replace the
Protective Relay
Verify CT Ratio in Equipment
Verify Connections on CT Wiring
Set to Correct Frequency
Check Trip Relay Wiring
Check that Trip Contact on Protective
Relay makes
Select Trip Test while in the Test Mode
Check Wiring from Protective Relay to
Circuit Breaker Trip Coil
Check that Circuit Breaker has Source of
Tripping Power
Replace Protective Relay
www.EatonElectrical.com
Initial Release
Reference
Paragraph 2-3
Paragraph 5-3
Paragraph 2-2
Paragraph 5-3
Paragraph 2-2.1
and 3-2
Paragraph 3-3.2
Paragraph 6-3
Paragraph 2-2.1
Paragraph 3-3.2
Paragraph 5-3
Paragraph 3-3.2
Paragraph 5-3
Paragraph 3-4
Paragraph 5-3
Paragraph 1-3
Figure 1-3
Paragraph 2-1.4
Figure 4-3
Paragraph 3-4
Wiring Plan
Drawing
Wiring Plan
Drawing
Paragraph 5-3