Connecting

Before connecting up and commissioning the device, read the information in the section
Safety instructions (Page 13)
NOTICE
Commissioning devices with redundancy mechanisms
If you use redundancy mechanisms ("HSR" media redundancy or "MRP" and/or redundant
coupling of rings over standby coupling), open the redundant path before you insert a new
or replacement device in an operational network. A bad configuration or attachment of the
Ethernet cables to incorrectly configured ports causes overload in the network and a
breakdown in communication.
A device may only be inserted in a network and connected in the following situations:
• HSR/MRP:
• Standby coupling:
6.1

Connecting the switch

Procedure for connecting the device
Follow the steps below to connect the device:
1. Turn off the power supply.
2. Connect the grounding of the switch according to the following description.
3. Connect the signaling contact of the switch according to the following description.
4. Connect the power supply of the switch according to the following description.
5. Connect the network nodes / subnets to the switch.
6. Turn on the power supply for the switch.
SCALANCE X-300
Operating Instructions, 02/2012, A5E01113043-12
WARNING
The ring ports of the device being inserted in the ring were configured as ring ports. The
required redundancy mode must also be enabled (see "Configuration Manual
SCALANCE X-300 / X-400", section "X-300 Ring Configuration"). If the device is
intended to operate as the redundancy manager, "Redundancy manager enabled" must
also be set.
"Standby connection" must be "enabled" and the "Standby connection name" must
match the name of the partner device. You will also need to configure the port with
"Enable Standby Port Monitoring" (see "Configuration Manual SCALANCE X-300 /
X-400", section "X-300/X-400 Standby Mask").