Cables
Cable assemblies, cable and connectors can be obtained from several manufacturers. To avoid
intermittent communications on the network, always connect DO and /DO via the same twisted pair.
Likewise, always connect DI and /DI via the same twisted pair. In addition, always connect both ends
of the cable shielding to their prespective connector housings or shield connection. A connection of 24
volts to data lines will permanently damage the module.
Remote Out
PIN 5
PIN 1
PIN 9
PIN 6
Male D-Sub
Connector
Housing
Solder Side
REMOTE OUT
Remote In
Pair
Yellow
1
DO
PIN 1
Green
Pair
6
/DO
Gray
2
DI
Pink
7
/DI
Brown
3
COM
PIN 6
Connector
Housing
REMOTE IN
PLC Comm Errors
In the event of a communication problem, error messages are displayed on a status line at the bottom
of the display.
Error Displayed Definition
PLC COMM ERROR (02:FF:A0) Error initializing Anybus module
PLC COMM ERROR (02:FF:01) Incorrect Anybus module ID
PLC COMM ERROR (02:FF:02) Anybus module watchdog time-out (module lockup)
PLC COMM ERROR (02:FF:03) Network Error - Network not connected