3.6 Installation and service
The menu is can be opened by entering code 1234�
3.6.1 Alarm/Service reminder
The service reminder function with preset intervals can be acti-
vated and shows the "Service reminder" text on the Premium
control panel display screen� The factory setting indicates that
the Service reminder is not in use� It can be put into operation
from the Installation and service menu, Service reminder point�
The normal setting is that the service reminder is displayed at
six month intervals; however the time setting is adjustable�
Reset the service reminder to zero from the Installation and
service menu, Alarm point, when service has been carried out�
Alarms for malfunctions are displayed in the display�
3.6.2 Clock
"On" or "Off"�
The clock is shown in the base image�
3.6.3 Temperature
"On" or "Off"�
The supply air temperature control function is shown in the
base image� Select ON in order to use the function for setting
the supply air temperature, otherwise select Off�
3.6.4 Measurements
Depending on the accessories connected, you can measure
the carbon dioxide content (CO
ferential, fan speeds, relative humidity (RH) and control signal
connection�
3.6.5 Control functions
Carbon dioxide content (CO
be selected as a control means�
3.6.6 Fan speeds
N.B.! The Summer night cooling function should be de-
activated whenever you change the fan speeds.
One of five fan modes (1–5) can be selected for each operat-
ing mode (Away, Home, Boost etc�)�
The various fan mode speeds (expressed as a percentage:
10–100) can then be selected (separate for supply air and
extract air)�
Basic display 1
Three fan speeds (Away, Home and Boost) can be utilized�
Basic display 2
Five fan speeds can be utilized�
3.6.7 To switch off the unit
The ventilation unit fans, the heat exchanger and an air heater,
if fitted, are stopped� The circuit card is however still energised
and the settings are preserved in the memory�
3.6.8 Factory settings
All settings except the fan speeds are reset to factory values�
3.6.9 Actuators/regulation modes
It is possible to select settings for duct equipment, the valve
actuators or circulation air regulation�
3.6.10 Functions
• Select ON as the value for Low pressure compensation, e�g�
if the cooker hood has a differential pressure guard in the
extract air duct of the cooker hood for this function, other-
wise select OFF�
• Select ON as the value for Service reminder, if the func-
16
www�swegon�com
), temperature, pressure dif-
2
), supervision (DDC) or timer can
2
3.6 Installation and service
(code 1234)
• Alarm/Service reminder
• Time switch clock (timer)
• Temperature
• Measurements
• Control functions
• Fan speeds
• Switch off
• Factory settings
• Controller
• Functions
• Air heater
tion is to be used, otherwise select Off� The time interval (6
months) can be changed�
• Select ON as the value for Summer night cooling, if you
wish to select the function in the menu, otherwise select
Off�
• Select On as the value for Heating, if an air heater is
installed, otherwise select Off� The limit value for high
temperature is 50 °C� The temperature can be changed�
Supply air fan ctrl is selected as the control means, this can
be changed to Room controlled�
• Select On as the value for Filter guard� (No R85)
• Select ON as the value for Fireplace function, if you intend
to use this function, otherwise select Off� The fireplace
switch function decreases the extract air fan speed and
increases the supply air fan speed� The freeze protection
works in the reverse manner: It reduces the speed of the
supply air fan and lets the extract air fan continue operating
at the same speed�
• Select ON as the value for Boost, if a boost timer or a pres-
ence detector is installed, otherwise select OFF�
3.6.11 Electric air heater (optional equipment)
Select ON as the value for Electric air heater, otherwise select
Off� Select 10 °C as the value for Outdoor air temp� This
means that the air heater will not be activated, when the
outdoor air temperature exceeds 10 °C °C� The temperature
limit can be changed�
The temperature sensor, T2, for sup-
ply air temporary decreases the fan speed
if the supply air becomes too cold. If the
supply air temperature drops below +11 °C,
the controller stops the supply air fan (this
protects against moisture condensing on
the exterior surfaces of the supply air duct).