ADVANCED FUNCTIONS
4.2 - PARAMETERS TABLE.
Parameters and description
UNIT CONTROL
Unit status (1=ON ó 0=standby)
Status auto /manual (0=Manual ó 1=Automatic)
Status cooling / heating (1=Cooling or 0=Heating )
(Writting is possible only with auto/manual = 0 manual)
CL40 cooling setpoint (with auto/manual = 0 manual)
CL40 heating setpoint (with auto/manual = 0 manual)
CL40 Auto setpoint (with auto/manual = 1 auto)
CL40 Second cooling setpoint
CL40 Second heating setpoint
Fan indoor operation mode
1 = always ON 2 = Automatic 3 = Anti-stratification
WARNING: Do not change this value into 0, otherwise fan
will be desactivated
Defrost status
0= Without defrost cycle
2= Defrost cycle circuit 2
5= Fan in defrost cycle circ.1
15= Fan in defrost cycle circ.1 and 2
Low noise activation
0= disabled
1= enable in cooling
2= enable in heating
Minimum configuration of fresh air
0= disabled
1= with freecooling enable
6= with freecooling disabled
8= cooling mode
9= heating mode
Minimum fresh air %
CLOCK CONFIGURATION
Real time : hours
Real time : minutes
Real time: day
Real time : month
Real time: year
Start hours for 2nd set point in cooling
Start minutes for 2nd set point in cooling
End hours for 2nd set point in cooling
End minutes for 2nd set point in cooling
Start houts for 2nd set point in heating
Start minutes for 2nd set point in heating
End hours for 2nd set point in heating
End minutes for 2nd set point in heating
Start hours for 2nd set point low noise cooling
Start minutes for 2nd set point low noise cooling
End hours for 2nd set point low noise cooling
End minutes for 2nd set point low noise cooling
Start hours for 2nd set point low noise heating
Start minutes for 2nd set point low noise heating
End hours for 2nd set point low noise heating
End minutes for 2nd set point low noise heating
1= Defrost cycle 1
3= Defrost cycle 1 y 2
10= Fan in defrost cycle. circ.2
3= enable in cooling and heating
7= always
min.
máx.
U.O.M.
0

Flag
0
8
Flag
0

Flag
*
*
ºC
*
*
ºC
*
*
ºC
*
*
ºC
*
*
ºC
0
5
Flag
0
255
Flag
0
3
Flag
0
9
Flag
0
00
%
0
23
h
0
59
min
0
3
día
0
2
mes
0
99
año
0
23
h
0
59
min
0
23
h
0
59
min
0
23
h
0
59
min
0
23
h
0
59
min
0
23
h
0
59
min
0
23
h
0
59
min
0
23
h
0
59
min
0
23
h
0
59
min
3
Modbus
resol.
R/W
address

R/W
64

R/W
29

R/W
65
0.
R/W
4
0.
R/W
43
0.
R/W
6
0.
R/W
55
0.
R/W
56

R/W
263

R
34

R/W
292

R/W
326

R/W
327

R/W
336

R/W
337

R/W
338

R/W
339

R/W
340

R/W
299

R/W
300

R/W
30

R/W
302

R/W
303

R/W
304

R/W
305

R/W
306

R/W
307

R/W
308

R/W
309

R/W
30

R/W
3

R/W
32

R/W
33

R/W
34
Type of
variable
Digital
Analog
Digital
Analog
Analog
Analog
Analog
Analog
Analog
Analog
Analog
Analog
Analog
Analog
Analog
Analog
Analog
Analog
Analog
Analog
Analog
Analog
Analog
Analog
Analog
Analog
Analog
Analog
Analog
Analog
Analog
Analog
Analog
Analog