Chimney Termination Requirements; 2-10-3 Rule - Quadra-Fire Discovery I Wood Appliance Installation Manual

Small wood stove
Table of Contents

Advertisement

B. Chimney Termination Requirements
Follow manufacturer's instructions for clearance, securing
flashing and terminating the chimney. Fig. 11.1 & 11.2
Must have an approved and Listed cap
Must not be located where it will become plugged by
snow or other material
Must terminate at least 3 feet (91cm) above the roof
and at least 2 feet (61cm) above any portion of the
roof within 10 feet (305cm).
Must be located away from trees or other structures
NOTICE:
• Chimney performance may vary.
• Trees, buildings, roof lines and wind conditions affect
performance.
• Chimney height may need adjustment if smoking or
overdraft occurs.
3 ft. (91cm)
Minimum
Figure 11.1
Figure 11.2
Augsut 01, 2016
2 ft. (61cm)
10 ft. (305cm) To Nearest Roofline
10 ft. (305cm) or more
Wall or Parapet
3 ft. (91cm) Minimum
NOTICE: Locating the appliance in a basement or in a
location of considerable air movement can cause intermittent
smoke spillage from appliance. Do not locate appliance near
Frequently open doors
Central heat outlets or returns
C. 2-10-3 Rule
These are safety requirements and are not meant to
assure proper flue draft.
This appliance is made with a 6 inch (152mm) diameter
chimney connector as the flue collar on the appli-
ance.
• Changing the diameter of the chimney can affect draft
and cause poor performance.
• It is not recommended to use offsets and elbows at
altitudes above 4000 feet above sea level and or when
there are other factors that affect flue draft.
Less than 10 ft. (305cm)
Pitched Roof
3 ft. (91cm) Minimum
Flat Roof
7039-174C
2 ft. (61cm)
3 ft. (91cm)
Minimum
Less than 10 ft. (305cm)
2 ft. (61cm) Minimum